EasyManua.ls Logo

Cumberland Evolution 4000 - Timers & Clocks - MAIN SYSTEM

Default Icon
86 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Part No. 4801-5338 Rev 2-2015 Evolution 4000 17 of 86
(1)Light Schedule
(2)Feed Schedule
(3)MINIMUM TIMERS:
(4)Cycle= 5 m ( 300s)
(8)VARIABLE SPEED:
(5)Min1%= 40% ( 215s)
(9)V1 Min%= 50%( 55%)
(6)Min2%= 20% ( 108s)
(10)V2 Min%= 40%(100%)
(7)Var%: 20% ( 108s)
(11)VARIABLE TIMER:
(12)Sensors = Outside-
(13)Max Run % = 65%
(14)Max Temp = 85.0°
(15)Min Run % = 20%
(16)Min Temp = 70.0°
(17)COOL TIMER:
(18)Max Run % = 100%
(19)Cycle = 10 m ( 600s)
(20)Min Run % = 55%
NOTE: Cycle in seconds
NOTE: Run Time in seconds
6.3 Timers & Clocks MAIN SYSTEM
The Minimum Vent status screen display:
(1) Light Schedule Displays the current Light Clock
Schedule. See Section 7.13.
(2) Feed Schedule Displays the current Feed Clock
Schedule. See Section 7.12.
(3) Minimum Timer 1 - The Minimum timer one and
two both share the same cycle time. Different timer
percentages may be set for minimum 1 vs. minimum
2. If the vent anticipation is being used, the vents
will start opening before a negative ventilation stage
turns on and will adjust until the vent opening
necessary for the desired target pressure is achieved.
(4) Cycle - The length of Timer 1 cycle. Cycle = 1 to
20 minutes.
(5) Min1 % - The percentage of the Timer 1 cycle that
the stage will run.
(6) Min2 % - The percentage of the Timer 2 cycle that
the stage will run.
(7) Var % - The percentage of time a stage is currently
running using the variable timer based off the
temperature.
NOTE: The Minimum timer one and two both share
the same cycle time. Different timer percentages
may be set for Minimum 1 and Minimum 2. If the
vent anticipation is being used, both Minimum 1 and
Variable will start the vents open before a stage
comes on.
(8) Variable Speed: These settings are used to set up
variable speed fan operation.
(9) V1 Minimum - The minimum speed or minimum
percentage of light intensity for V1; The value
inside the parenthesis shows the current percentage.
(10) V2 Minimum -The minimum speed or minimum
percentage of light intensity for V2; The value
inside the parenthesis shows the current percentage.
(11) Variable Timer - The variable timer will vary the
timer based on temperature. See chart shown
below.
(12) Sensors - The sensors used to determine the run
time. Active sensors will be indicated by a number
starting with #1 from right to left. Inactive sensors
will be indicated by a - or hyphen. When "outside-"
is displayed, outside sensor is active. For example, If
sensors 1, 2 and 3 are being used, "-----321" will be
displayed. When “outside” is displayed, the outside
sensor is active.
(13) Max Run % - The maximum Run Time
percentage.
(14) Max Temp - The temperature at which the timer
will run Maximum Run time % percentage.
(15) Min Run % - The minimum Run Time
percentage.
(16) Min Temp - The minimum temperature. The
timer will be at minimum Run %.

Table of Contents

Related product manuals