EasyManua.ls Logo

Daikin AZQS100B8V1B - Refrigerant Piping Connection Guidelines

Daikin AZQS100B8V1B
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6Installation
Installerreferenceguide
11
AZQS100~140B8V1B+AZQS100~140B7Y1B
Splitsystemairconditioners
4P3855291–2014.08
â–Ș Keepinginmindtheguidelinesfor:
â–Ș Pipebending
â–Ș Flaringpipeends
â–Ș Brazing
â–Ș Usingthestopvalves
6.4.2 Precautionswhenconnectingthe
refrigerantpiping
INFORMATION
Also read the precautions and requirements in the
followingchapters:
â–Ș Generalsafetyprecautions
â–Ș Preparation
DANGER:RISKOFBURNING
CAUTION
â–Ș DoNOTusemineraloilonflaredpart.
â–Ș NEVER install a drier to this R410A unit to guarantee
its lifetime. The drying material may dissolve and
damagethesystem.
NOTICE
Take the following precautions on refrigerant piping into
account:
â–Ș Avoid anything but the designated refrigerant to get
mixedintotherefrigerantcycle(e.g.air).
â–Ș OnlyuseR410Awhenaddingrefrigerant.
â–Ș Onlyuseinstallationtools(e.g.manifoldgaugeset)that
are exclusively used for R410A installations to
withstandthepressureandtopreventforeignmaterials
(e.g. mineral oils and moisture) from mixing into the
system.
â–Ș Installthepipingsothatthe flare is NOT subjected to
mechanicalstress
â–Ș Protectthepipingasdescribedinthefollowingtableto
preventdirt,liquidordustfromenteringthepiping.
â–Ș Usecaution whenpassingcopper tubesthroughwalls
(seefigurebelow).
Unit Installationperiod Protectionmethod
Outdoorunit >1month Pinchthepipe
<1month Pinchortapethepipe
Indoorunit Regardlessofthe
period
INFORMATION
Do NOT open the refrigerant stop valve before checking
therefrigerantpiping.Whenyouneedtochargeadditional
refrigerantitisrecommendedto open the refrigerant stop
valveaftercharging.
6.4.3 Guidelineswhenconnectingthe
refrigerantpiping
Takethefollowingguidelinesintoaccountwhenconnectingpipes:
â–Ș Coat the flare inner surface with ether oil or ester oil when
connecting a flare nut. Tighten 3 or 4 turns by hand, before
tighteningfirmly.
â–Ș Alwaysusetwowrenchestogetherwhenlooseningaflarenut.
â–Ș Alwaysuse a spannerandtorque wrenchtogetherto tightenthe
flarenutwhenconnectingthepiping.Thistopreventnutcracking
andleaks.
a
b
c
d
a Torquewrench
b Spanner
c Pipingunion
d Flarenut
Pipingsize
(mm)
Tightening
torque(N‱m)
Flare
dimensions(A)
(mm)
Flareshape
(mm)
Ø6.4 15~17 8.7~9.1
R=0.4~0.8
45°
±2
90°
±2
A
Ø9.5 33~39 12.8~13.2
Ø12.7 50~60 16.2~16.6
Ø15.9 63~75 19.3~19.7
Ø19.1 90~110 23.6~24.0
6.4.4 Pipebendingguidelines
Usea pipebenderfor bending.All pipebendsshould beasgentle
aspossible(bendingradiusshouldbe30~40mmorlarger).
6.4.5 Toflarethepipeend
CAUTION
â–Ș Incompleteflaringmaycauserefrigerantgasleakage.
â–Ș Do NOT reuse flares. Use new flares to prevent
refrigerantgasleakage.
â–Ș Use flare nuts that are included with the unit. Using
differentflarenutsmaycauserefrigerantgasleakage.
1 Cutthepipeendwithapipecutter.
2 Removeburrswiththecutsurfacefacingdownwardsothatthe
chipsdonotenterthepipe.
a b
a Cutexactlyatrightangles.
b Removeburrs.
3 Removethe flarenutfromthestopvalveandputtheflarenut
onthepipe.
4 Flare the pipe. Set exactly at the position as shown in the
followingillustration.
A

Table of Contents