7Commissioning
Installerreferenceguide
20
AZQS100~140B8V1B+AZQS100~140B7Y1B
Splitsystemairconditioners
4P3855291–2014.08
6.8.2 Toclosetheoutdoorunit
NOTICE
When closing the outdoor unit cover, make sure that the
tighteningtorquedoesNOTexceed4.1N•m.
6.8.3 Tochecktheinsulationresistanceofthe
compressor
NOTICE
If, after installation, refrigerant accumulates in the
compressor, the insulation resistance over the poles can
drop,butifitisatleast1MΩ,thentheunitwill notbreak
down.
▪ Usea500Vmegatesterwhenmeasuringinsulation.
▪ Donotuseamegatesterforlowvoltagecircuits.
1 Measuretheinsulationresistanceoverthepoles.
If Then
≥1MΩ InsulationresistanceisOK.Thisprocedure
isfinished.
<1MΩ InsulationresistanceisnotOK.Gotothe
nextstep.
2 TurnONthepowerandleaveitonfor6hours.
Result: The compressor will heat up and evaporate any
refrigerantinthecompressor.
3 Measuretheinsulationresistanceagain.
7 Commissioning
7.1 Overview:Commissioning
This chapter describes what you have to do and know to
commissionthesystemafteritisinstalled.
Typicalworkflow
Commissioningtypicallyconsistsofthefollowingstages:
1 Checkingthe"Checklistbeforetestrun".
2 Performingatestrunforthesystem.
7.2 Precautionswhencommissioning
INFORMATION
During the first running period of the unit, the required
powermaybehigherthanstatedonthenameplateofthe
unit.This phenomenoniscaused bythe compressor,that
needs a continuous run time of 50 hours before reaching
smoothoperationandstablepowerconsumption.
NOTICE
Beforestartingupthesystem,theunitMUSTbeenergised
for at least 6 hours. The crankcase heater needs to heat
up the compressor oil to avoid oil shortage and
compressorbreakdownduringstartup.
NOTICE
NEVER operate the unit without thermistors and/or
pressure sensors/switches. Burning of the compressor
mightresult.
NOTICE
Do NOT operate the unit until the refrigerant piping is
complete (when operated this way, the compressor will
break).
NOTICE
Coolingoperation mode.Performthe testrunincooling
operationmodesothatstopvalvesfailingtoopencanbe
detected. Even if the user interface was set to heating
operationmode,theunitwillrunincoolingoperationmode
during23minutes(althoughtheuserinterfacewilldisplay
theheatingicon),andthenautomaticallyswitchtoheating
operationmode.
NOTICE
If you cannot operate the unit in test run, see "7.5 Error
codeswhenperformingatestrun"onpage21.
WARNING
Ifthepanelsontheindoorunitsarenotinstalledyet,make
sureto powerOFF thesystem afterfinishing thetestrun.
To do so, turn OFF operation via the user interface. Do
NOTstopoperationbyturningOFFthecircuitbreakers.
7.3 Checklistbeforetestrun
DoNOToperatethesystembeforethefollowingchecksareOK:
Theindoorunitsareproperlymounted.
Incaseawirelessuserinterfaceisused:Theindoorunit
decorationpanelwithinfraredreceiverisinstalled.
Theoutdoorunitisproperlymounted.
Thefollowingfieldwiringhasbeencarriedoutaccording
tothisdocumentandtheapplicablelegislation:
▪ Betweenthelocalsupplypanelandtheoutdoorunit
▪ Betweentheoutdoorunitandtheindoorunit
ThereareNOmissingphasesorreversedphases.
The system is properly earthed and the earth terminals
aretightened.
The fuses or locally installed protection devices are
installed according to this document, and have not been
bypassed.
The power supply voltage matches the voltage on the
identificationlabeloftheunit.