12.2.2 Servicespace:Outdoorunit
Suctionside Intheillustrationsbelow,theservicespaceatthesuctionsideisbasedon35°CDBandcoolingoperation.Forsee
morespaceinthefollowingcases:
Whenthesuctionsidetemperatureregularlyexceedsthistemperature.
Whentheheatloadoftheoutdoorunitsisexpectedtoregularlyexceedthemaximumoperatingcapacity.
Dischargeside Takerefrigerantpipingworkintoaccountwhenpositioningtheunits.Ifyourlayoutdoesnotmatchanyofthe
layoutsbelow,contactyourdealer.
Singleunit|Singlerowofunits
Layout If Then(mm)
Obstacles Heights a b c d e e
B
e
D
Singleunit
a
b
c
d
e
e
B
e
D
A
B
C
D
E
H
B
H
U
H
D
B ≥100
A,B,C ≥100 ≥100 ≥100
B,E ≥100 ≥1000 ≤500
A,B,C,E ≥150 ≥150 ≥150 ≥1000 ≤500
D ≥500
D,E ≥500 ≥1000 ≤500
B,D H
B
<H
D
H
D
>H
U
≥100 ≥500
H
B
>H
D
H
D
<H
U
≥100 ≥500
B,D,E
(Note1)
H
B
<H
D
H
B
≤½H
U
≥250 ≥750 ≥1000 ≤500
½H
U
<H
B
≤H
U
≥250 ≥1000 ≥1000 ≤500
H
B
>H
U
NOTallowed
H
B
>H
D
H
D
≤½H
U
≥100 ≥1000 ≥1000 ≤500
½H
U
<H
D
≤H
U
≥200 ≥1000 ≥1000 ≤500
H
D
>H
U
NOTallowed
Singlerowofunits
H
U
a
b
>100
c
d
e
e
B
e
D
A
B
C
D
E
H
B
H
D
>100
A,B,C ≥200 ≥300 ≥1000
A,B,C,E ≥200 ≥300 ≥1000 ≥1000 ≤500
D ≥1000
D,E ≥1000 ≥1000 ≤500
B,D H
B
<H
D
H
D
>H
U
≥300 ≥1000
H
B
>H
D
H
D
≤½H
U
≥250 ≥1500
½H
U
<H
D
≤H
U
≥300 ≥1500
B,D,E
(Note1)
H
B
<H
D
H
B
≤½H
U
≥300 ≥1000 ≥1000 ≤500
½H
U
<H
B
≤H
U
≥300 ≥1250 ≥1000 ≤500
H
B
>H
U
NOTallowed
H
B
>H
D
(Note2)
H
D
≤½H
U
≥250 ≥1500 ≥1000 ≤500
½H
U
<H
D
≤H
U
≥300 ≥1500 ≥1000 ≤500
H
D
>H
U
NOTallowed
A,B,C,D Obstacles(walls/baffleplates)
E Obstacle(roof)
a,b,c,d,e MinimumservicespacebetweentheunitandobstaclesA,B,C,DandE
e
B
MaximumdistancebetweentheunitandtheedgeofobstacleE,inthedirectionofobstacleB
e
D
MaximumdistancebetweentheunitandtheedgeofobstacleE,inthedirectionofobstacleD
H
U
Heightoftheunit
H
B
,H
D
HeightofobstaclesBandD
Note1 Sealthebottomoftheinstallationframetopreventdischargedairfromflowingbacktothesuctionsidethroughthebottomoftheunit.
Note2 Maximumtwounitscanbeinstalled.

Table of Contents

Other manuals for Daikin AZQS100B8V1B

Related product manuals