EasyManua.ls Logo

Daikin AZQS100B8V1B - Using Stop Valves and Service Ports

Daikin AZQS100B8V1B
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6Installation
Installerreferenceguide
12
AZQS100~140B8V1B+AZQS100~140B7Y1B
Splitsystemairconditioners
4P3855291–2014.08
Conventionalflaretool
Flaretoolfor
R410A(clutch
type)
Clutchtype
(Ridgidtype)
Wingnuttype
(Imperialtype)
A 0~0.5mm 1.0~1.5mm 1.5~2.0mm
5 Checkthattheflaringisproperlymade.
a b
c
a Flare’sinnersurfacemustbeflawless.
b Thepipeendmustbeevenlyflaredinaperfectcircle.
c Makesuretheflarenutislifted.
6.4.6 Tobrazethepipeend
The indoor unit and outdoor unit have flare connections. Connect
both ends without brazing. If brazing should be needed, take the
followingintoaccount:
When brazing, blow through with nitrogen to prevent creation of
large quantities of oxidised film on the inside of the piping. This
filmadverselyaffectsvalvesandcompressorsintherefrigerating
systemandpreventsproperoperation.
Setthenitrogenpressureto20kPa(justenoughsoitcanbefelt
ontheskin)withapressurereducingvalve.
a b c d e
f
f
a Refrigerantpiping
b Parttobebrazed
c Taping
d Manualvalve
e Pressurereducingvalve
f Nitrogen
DoNOTuseantioxidantswhenbrazingpipejoints.
Residuecanclogpipesandbreakequipment.
Do NOT use flux when brazing coppertocopper refrigerant
piping. Use phosphor copper brazing filler alloy (BCuP), which
doesnotrequireflux.
Flux has an extremely harmful influence on refrigerant piping
systems.Forinstance,ifchlorinebasedfluxisused,itwillcause
pipe corrosion or, in particular, if the flux contains fluorine, it will
deterioratetherefrigerantoil.
6.4.7 Usingthestopvalveandserviceport
Tohandlethestopvalve
Takethefollowingguidelinesintoaccount:
Thestopvalvesarefactoryclosed.
Thefollowingillustrationshowseachpartrequiredinhandlingthe
valve.
c
d
a
b
a Serviceportandserviceportcap
b Valvestem
c Fieldpipingconnection
d Stemcap
Keepbothstopvalvesopenduringoperation.
Do NOT apply excessive force to the valve stem. Doing so may
breakthevalvebody.
Alwaysmakesure tosecurethe stopvalvewith a spanner,then
loosenortightentheflarenutwithatorquewrench.DoNOTplace
the spanner on the stem cap, as this could cause a refrigerant
leak.
a
b
a Spanner
b Torquewrench
When it is expected that the operating pressure will be low (e.g.
whencooling willbe performedwhiletheoutsideairtemperature
islow),sufficientlysealtheflarenut inthestopvalveonthegas
linewithsiliconsealanttopreventfreezing.
Siliconsealant,makesurethereisnogap.
Toopen/closethestopvalve
1 Removethevalvecover.
2 Insert a hexagon wrench (liquid side: 4 mm, gas side: 6 mm)
intothevalvestemandturnthevalvestem:
Counterclockwisetoopen.
Clockwisetoclose.
3 Whenthevalvestemcannotbeturnedanyfurther,stopturning.
Thevalveisnowopened/closed.
Tohandlethestemcap
Takethefollowingguidelinesintoaccount:
Thestem capissealed whereindicated withthearrow. DoNOT
damageit.
Afterhandling the stopvalve,make suretotighten the stemcap
securely.
Forthetighteningtorque,refertothefollowingtable.
Checkforrefrigerantleaksaftertighteningthestemcap.
Item Tighteningtorque(N∙m)
Stemcap,liquidside 13.5~16.5
Stemcap,gasside 22.5~27.5
Serviceportcap 11.5~13.9

Table of Contents

Other manuals for Daikin AZQS100B8V1B

Related product manuals