8Handovertotheuser
Installerreferenceguide
21
AZQS100~140B8V1B+AZQS100~140B7Y1B
Splitsystemairconditioners
4P3855291–2014.08
ThereareNOlooseconnectionsor damaged electrical
componentsintheswitchbox.
TheinsulationresistanceofthecompressorisOK.
There are NO damaged components or squeezed
pipesontheinsideoftheindoorandoutdoorunits.
ThereareNOrefrigerantleaks.
The correct pipe size is installed and the pipes are
properlyinsulated.
Thestopvalves(gasandliquid)ontheoutdoorunitare
fullyopen.
7.4 Toperformatestrun
NOTICE
Donotinterruptthetestrun.
INFORMATION
In case you have to redo the test run, see the service
manual.
1 Performintroductorysteps.
# Action
1 Opentheliquidstopvalve(A)andgasstopvalve(B)
byremovingthestemcapandturning
counterclockwisewithahexwrenchuntilitstops.
2 Closetheservicecovertopreventelectricshocks.
3 TurnONpowerforatleast6hoursbeforestarting
operationtoprotectthecompressor.
4 Ontheuserinterface,settheunittocoolingoperation
mode.
2 Ontheuserinterface,turnONtheunit.
Result: The test run starts automatically. During the test run,
the H2P test LED is ON. When the test run is done, the LED
turnsOFF.
7.5 Errorcodeswhenperforminga
testrun
Iftheinstallationoftheoutdoorunit has NOT been done correctly,
thefollowingerrorcodesmaybedisplayedontheuserinterface:
Errorcode Possiblecause
Nothingdisplayed
(thecurrentlyset
temperatureisnot
displayed)
▪ The wiring is disconnected or there is a
wiring error (between power supply and
outdoor unit, between outdoor unit and
indoor units, between indoor unit and
userinterface).
▪ The fuse on the outdoor unit PCB has
blownout.
E3,E4orL8 ▪ Thestopvalvesareclosed.
▪ Theairinletorairoutletisblocked.
Errorcode Possiblecause
E7 Thereisamissingphaseincaseofthree
phasepowersupplyunits.
Note:Operationwillbeimpossible.Turn
OFFthepower,recheckthewiring,and
switchtwoofthethreeelectricalwires.
L4 Theairinletorairoutletisblocked.
U0 Thestopvalvesareclosed.
U2 ▪ Thereisavoltageimbalance.
▪ There is a missing phase in case of
threephase power supply units. Note:
Operation will be impossible. Turn OFF
thepower,recheckthewiring,andswitch
twoofthethreeelectricalwires.
U4orUF Theinterunitbranchwiringisnotcorrect.
UA Theoutdoorandindoorunitare
incompatible.
NOTICE
▪ Thereversedphaseprotectiondetectorofthisproduct
only functions when the product starts up.
Consequently reversed phase detection is not
performedduringnormaloperationoftheproduct.
▪ Thereversed phaseprotectiondetector isdesignedto
stop the product in the event of an abnormality when
theproductisstartedup.
▪ Replace two of the three phases (L1, L2, and L3)
duringreversephaseprotectionabnormality.
8 Handovertotheuser
Oncethetestrunisfinishedandthe unitoperatesproperly,please
makesurethefollowingisclearfortheuser:
▪ Make sure that the user has the printed documentation and ask
him/hertokeepitforfuturereference.Informtheuserthathecan
findthecompletedocumentationontheurlasearlierdescribedin
thismanual.
▪ Explaintheuserhowtoproperlyoperatethesystemandwhathe/
shehastodoincaseofproblems.
▪ Showtheuserwhathe/shehastodoinrelationtomaintainingthe
unit.
9 Maintenanceandservice
NOTICE
Maintenanceshouldpreferablybecarriedoutyearlybyan
installerorserviceagent.
9.1 Overview:Maintenanceand
service
Thischaptercontainsinformationabout:
▪ Theyearlymaintenanceoftheoutdoorunit