12Technicaldata
Installerreferenceguide
37
AZQS100~140B8V1B+AZQS100~140B7Y1B
Splitsystemairconditioners
4P3855291–2014.08
AZQS100_V1 AZQS125_V1 AZQS140_V1
Control Expansionvalve(electronictype)
Nr.ofcircuits 1
Refrigerantoil
Type FVC50K
Chargedvolume 0.9l 1.35l
PED
Categoryofunit 1
ExcludedfromPEDduetoarticle1,item3.6of97/23/EC
Pipingconnections
Liquid Quantity 1
Type Flareconnection
Diameter(OD) Ø9.52mm
Gas Quantity 1
Type Flareconnection
Diameter(OD) Ø15.9mm
Drain Quantity 5
Type Hole
Diameter(OD) Ø26mm
Pipinglength Minimum 5m
Maximum 50m
Equivalent 70m
Chargeless 30m
Additionalrefrigerantcharge See"Todeterminetheadditionalrefrigerantamount"
Maximumheightdifferencebetweenoutdoor
unitandindoorunit
30m
Maximuminterunitleveldifference 0.5m
Heatinsulation Bothliquidandgaspipes
Defrostmethod Reversecycle
Defrostcontrol Sensorforoutdoorheatexchangertemperature
Capacitycontrolmethod Invertercontrolled
Capacitycontrol
Cooling Minimum
Maximum
Heating Minimum
Maximum
Safetydevices Highpressureswitch/lowpressureswitch/fanmotorthermalprotector/fuse
Standardaccessories 1installationmanual/2tiewraps
Electricalspecifications:AZQS_V1
AZQS100_V1 AZQS125_V1 AZQS140_V1
Powersupply
Name V1
Phase 1~
Frequency 50Hz
Voltage 220240V
Voltagerange Minimum 198V
Maximum 264V
Current
Nominalrunningcurrent
Startingcurrent
Z
max
CompliestoEN61000311
MinimumS
sc
value EquipmentcomplyingwithEN61000312
(a)
Maximumrunningcurrent
Recommendedfuses 32A 40A
Wiringconnections