12Technicaldata
Installerreferenceguide
37
AZQS100~140B8V1B+AZQS100~140B7Y1B
Splitsystemairconditioners
4P3855291–2014.08
AZQS100_V1 AZQS125_V1 AZQS140_V1
Control Expansionvalve(electronictype)
Nr.ofcircuits 1
Refrigerantoil
Type FVC50K
Chargedvolume 0.9l 1.35l
PED
Categoryofunit 1
ExcludedfromPEDduetoarticle1,item3.6of97/23/EC
Pipingconnections
Liquid Quantity 1
Type Flareconnection
Diameter(OD) Ø9.52mm
Gas Quantity 1
Type Flareconnection
Diameter(OD) Ø15.9mm
Drain Quantity 5
Type Hole
Diameter(OD) Ø26mm
Pipinglength Minimum 5m
Maximum 50m
Equivalent 70m
Chargeless 30m
Additionalrefrigerantcharge See"Todeterminetheadditionalrefrigerantamount"
Maximumheightdifferencebetweenoutdoor
unitandindoorunit
30m
Maximuminterunitleveldifference 0.5m
Heatinsulation Bothliquidandgaspipes
Defrostmethod Reversecycle
Defrostcontrol Sensorforoutdoorheatexchangertemperature
Capacitycontrolmethod Invertercontrolled
Capacitycontrol
Cooling Minimum
Maximum
Heating Minimum
Maximum
Safetydevices Highpressureswitch/lowpressureswitch/fanmotorthermalprotector/fuse
Standardaccessories 1installationmanual/2tiewraps
Electricalspecifications:AZQS_V1
AZQS100_V1 AZQS125_V1 AZQS140_V1
Powersupply
Name V1
Phase 1~
Frequency 50Hz
Voltage 220240V
Voltagerange Minimum 198V
Maximum 264V
Current
Nominalrunningcurrent
Startingcurrent
Z
max
CompliestoEN61000311
MinimumS
sc
value EquipmentcomplyingwithEN61000312
(a)
Maximumrunningcurrent
Recommendedfuses 32A 40A
Wiringconnections