107
• Control systems
• intelligent Touch Manager • ED721208
Factory preset before shipment
C/C : Centralized control equipment
C/D : Connectable Devices or Facility equipment
Switch Condition Factory preset before shipment
DS1 Range of address No. 1-00, 01, 02, 03
DS2 A1 - AM Abnormal in the open condition
DS4-1 Power failure, then after power recovery Stop
DS4-2 Communication abnormal Stop
DS4-3 Last command priority or C/C only Last command priority
DS4-4
Operation commands from C/C reach to C/D , but no
operation.
No abnormality signal to C/C
DS5 Of abnormal in C/D, CD- D1~4 is “turned off”.
DS6-1
Mask time for abnormal input after operation command
from C/C
10 seconds
DS6-2 After error of C/D is recovered Automatic reset
DS6-3 Abnormal input + stop state of C/D Error display on C/C
DS6-4 Forced stop command from C/C C/D stop
SS1 Continuous output “Con” / Instantaneous output “Ins” Continuous output
TNa “a” contact or “b” contact for CD- D1~4 “a” contact
DS3 Number of C/D 4
“a” contact: make-contact, “b” contact: break-contact