2. Functions & Options
2.1. Functions
56
• Control systems
• Management control • DCM601A51 •
Category Function Remarks
Basicfunctions
iTM plus adaptor (DCM601A52) Maximumnumberofadaptors:7
Management points
Maximumnumberofmanagementpoints:650
(NumberofDIIIconnectionmanagementpoints:512)
Areas
Maximumnumberofareas:650
Maximum area hierarchies: 10
Supported languages English, French, German, Italian, Spanish, Portuguese, Dutch, Chinese, and Japanese
Monitoring screens
Icon view Iconsshowtheoperationstatusofequipment.
List view Detailedinformationofeachmanagementpointisdisplayed.
Layout view Up to 60 screens can be created.
History
Upto100,000eventsarerecordedinhistoryincludingmalfunctions,operations,
automaticcontrol,andsysteminformation.
Operation origin is also recorded.
Automatic control
Schedule
Numberofprogrammes:100
Up to 20 actions/day can be set.
Weekly schedule 7daysoftheweek+5specialdayscanbeset.
Yearly calendar
Specialdayscanbespecifiedbydateormonth/week/dayoftheweek.
Special day settings can be reused every year.
Seasonal schedule Programmesforrespectiveseasonscanbeswitchedbydate.
Interlock
Numberofprogrammes:500
Interlockispossibleforon/off,malfunction,analoguevalue,andoperationmode
switching.
Emergency stop Numberofprogrammes:31
Automatic changeover Numberofchangeovergroups:512
Temperature limit
Numberoftemperaturelimitgroups:8
Upper limit range: 32-50°C
Lower limit range: 2-16°C
Sliding temperature
Numberofslidingtemperaturegroups:8
Outdoor temperature range: 18-34 °c
Setpoint range: 16-32°C
Heating Mode Optimisation (HMO) Unneeded heating is prevented.
Timer extension Operationstopisselectablefrom30,60,90,120,and180minutes.
Setback
Setbacksetpointcanbesetfor2patterns.
Temperaturerange:1-7°C,-1--7°C(setpointshiftamount)
Data control
Power Proportional Distribution
Hourly Power Proportional Distribution results up to 13 months are recorded.
ThesystemsupportsdataoutputinCSVformat.
Energy Navigator
Actualresultsofdaily/monthlyenergyconsumptionareshowningraphs.
Comparisonscanbemadewithpredeterminedvalues/actualresultsoftheprevious
year.
InefficientoperationofVRVindoorunitsisautomaticallyidentified,andenergywaste
is calculated.
Remote access
Web access
WebbrowserscandisplaythesametypeofscreenastheintelligentTouchManager.
Up to 4 administrators and 60 general users can be registered.
Screens and operation accessible to general users can be restricted.
E-mail alerts
Up to 10 e-mail addresses can be set.
Addressesforsendingmalfunctionalertscanbesetbyrangeofmanagementpoints.
TheSMTPserverauthenticationmethodisselectablefromnoauthentication,
POPbeforeSMTP,andSMTP-AUTH.
System
Automatic registration
IndoorunitsconnectedtoDIII-NETareautomaticallydetected,andiconsfor
respective models are automatically registered.
Security
Screenlockfunctionsareavailable.
Accessrestrictionscanbesetforeachgeneraluser.
Screen savers Screensaversareselectablefrom3patterns.
Settingofcontactinformation Contactinformationforservicingcanberegistered.
Air Conditioning
Network Service
Air Conditioning Network Service System A service agreement needs to be concluded.
Energy Saving Air Conditioning Network Service
System
A service agreement needs to be concluded.

Table of Contents