Disassembly and Maintenance ESIE05-04
5–58 Part 5 – Disassembly and Maintenance
3
1
5
5
1.12.8 Removal of Drain Pan
Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work.
Procedure:
Step Procedure Points
1 Remove the drain socket
to drain water from the
drain hole.
2 Remove the 4 mounting
screws to remove the
drain pan.
Q Remove the drain socket to
drain water from the drain hole.
Q If water is in the drain pan, it
can spill and wet the floor.
Drain water completely or
cover the floor with a vinyl
sheet before removing the
drain pan.
3 Pull down the drain pan
straight down.
Drain socket
(S2658)
(S2659
)