EasyManua.ls Logo

Daikin RoCon HP - Heat Curve

Daikin RoCon HP
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operating instructions
22
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
3 x Operation
3.6.2 Heat curve
Caution - danger of overheating with
underfloor heating!
In the event of a fault, or in hand mode,
damage may be caused to the screed,
the structure of the floor and the under-
floor heating system by overheating.
Before initial commissioning of the
underfloor heating system, set the
maximum permissible system
temperature Controller RoCon HP
(parameter [T vbh1 max]) in the
maximum temperature limit in the
Control RoCon HP (parameter [Max
T-Flow]).
Connect the overheat protection
switch (customer) on the "EXT" plug
connection to the external operating
mode switch so that the Daikin
Altherma EHS(X/H) is in operating
mode "Standby" or "Summer"
(see section 3.4.2).
In parameter [Room thermostat] = On
or parameter [Interlink fct] = On, the
overheat protection switch must be
connected so that the switching con-
tact of the room thermostat is inter-
rupted.
If the underfloor heating system is
also used for room cooling, the
connection notes from the previous
section are also valid for the
connection of a customer-provided
humidity protection switch.
With the heating characteristic curve, the inflow target temper-
ature is adjusted to building conditi
ons in accordance with the rel-
evant external temperature (weather-controlled flow temperature
regulation, see section 3.6.4). Generally speaking, the steepness
of the heating characteristics describes the ratio of the flow tem-
perature change to the external temperature change.
The heating characteristic curve applies within the minimum and
maximum temperature li
mits that have been set for the corre-
sponding heating circuit. The room temperature measured in the
living area may differ from the desired room temperature; these
deviations can be kept to a minimum by installing a room station
or a room thermostat.
The Controller is con
figured in the factory so that the heating
curve does not adjust itself during operation.
The automatic heat curve adaptation can be activated
(parameter [HC Adaption]) if the room station (EHS157034) is
connected (see section 3.6.4).
Starting conditions for the automatic hea
ting curve adaption:
Outdoor temperature < 8 °C
Operating mode is automat
ic (I or II)
Duration of setback phase at least 6 hours
If an au
tomatic heat curve adaption is not activated, the heat
curve can be set manually by adjusting the parameter [Heat-
Slope]).
Manually adjusting the heating curve
Do not make any corrections to the set values for 1 - 2
days, and then only make them in small increments.
Deactivate additional heat sources (e.g. fireplaces,
direct solar radiation, open windows).
Fu
lly open any existing radiator thermostat valves
or setting drives.
Activa
te the operating mode "Heating".
Approximate setting values:
Radiator: 1.4 to 1.6.
Underfloor heating system: 0.5 to 0.9.

Related product manuals