6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
51
6.10 Rotary switch setting: Info
Parameter Description Access Setting range
Min / Max
Factory
setting
Increment
BE HF
Overview Display of different current operating data (see section 3.4.1). S S - - -
Water Pressure The current water pressure is displayed in bar. S S 0 - 4 bar - 0.1 bar
T-HS The current temperature (TVBH) of the heat generator is displayed in °C. S S 0 - 100 °C - 1 °C
T-HS Setpoint The current Inflow target temperature of the heat generator is displayed in °C
(see section 3.6.4).
S S 0 - 90 °C - 0.1 °C
T-Outside The average external temperature is displayed °C. S S -39 to +50 °C 0.1 °C
T-DHW The current temperature of the hot water storage tank is displayed in °C. If there is no hot
wat
er function activated, "- - -" is displayed.
S S 0 - 100 °C - 0.1 °C
T-DHW Setpoint The current target hot water temperature is displayed °C. If there is no hot water function ac-
tivated, "- - -" is displayed. The current set value is here always the maximum value of all
r
elevant demands for this hot water circuit.
S S 10 - 70°C - 0.1 °C
T-Return The current return flow temperature of the heat generator is displayed in °C. If there is no
r
elevant sensor connected to the heat generator, "- - -" is displayed.
S S 0 - 100 °C - 0.1 °C
Flow Rate The filtered value of the current volume flow in litres per hour is displayed. S S 0 - 5100 l/h - l/h
T-HC The inflow temperature in the direct heating circuit is displayed in °C. S S 0 - 100 °C - 0.1 °C
T-HC Setpoint The set temperature of the flow in the direct heating circuit is displayed in °C. S S 0 - 90
°C - 0.1 °C
Status HS pump The current status of the internal heat circulation pump in the Daikin Altherma EHS(X/H) is
d
isplayed.
S S Off
On
- -
Runtime Compres-
sor
The running time of the refrigerant compressor is displayed in h. S S - - h
Runtime Pump The running time of the internal heating circulation pump is displayed in h. S S - - h
Mixer Position The current position of the 3UV DHW 3-way switch valve is displayed.
0%: Position A (room heating)
100%: Position B (domestic hot water generation)
S S 0 - 100 % - 1 %
Qboh The amount of heat in the additional heat generator for hot water generation is displayed in
kWh.
S S - - kWh
Qchhp The amount of heat in the additional heat generator for heating mode is displayed in kWh. S S - - kWh
Qsc The quantity of heat in the heat pump for cooling is displayed in kWh. S S - - kWh
Qch The quantity of heat in the heat pump for heating is displayed in kWh. S S - - kWh
QWP The total amount of heat in the heat pump is displayed in kWh. S S - - kWh
Qdhw The quantity of heat for hot water generation is displayed in kWh. S S - - kWh
HS type The heat generator type Daikin Altherma EHS(X/H) detected is displayed. S S - - -
Sw Nr B1/U1 The software and version of the control unit RoCon B1 B1 /
of the room station
EHS157034is displayed.
S S - - -
Sw Nr Controller The software number and the version of the RoCon BM1 circuit board are displayed. S S - - -
Sw Nr RTX RT The software number and the version of the RTX-AL4 circuit board are displayed. S S - - -
Tab. 6-12 Parameter in rotary switch setting "Info"
6.11 Exit button: Sonderfunktion
Depress the exit button for at least 5 secs. for access.
Parameter Description Access Setting range
Min / Max
Factory
setting
Increment
BE HF
Manual Operation The direct heating circuit and the target hot water temperature are controlled according to
t
he temperature set in this parameter (see section 3.5.1).
E E 20 - 80 °C 50 °C 1 °C
FA failure Display of a current heat pump malfunction in the Daikin Altherma EHS(X/H).
If "----" is displayed there is no fault (see chapter 7).
E E - - -
Protocol Display of protocol (error and information messages). Here we display the saved messages
of the Daikin Altherma EHS(X/H) and the connected RoCon
system components with date
and code as a menu entry in each case. By selecting an entry to using the rotary switch, all
other corresponding information is displayed concerning the selected message:
- Date and time of the message
- Code number (Information for the heating technician)
- Device type from which the message comes
- Device ID for the RoCon unit where the message originates
E E - - -
Delete message By setting this parameter to "On" and briefly pressing the rotary switch, all entries in the re-
port, including the faults from connected RoCon system components, are deleted.
E E Off
On
Off -
RoCon B1/U1 Reset Resets all parameter settings to factory setting. Required for software updates or changes
to the RoCon system (see chapter 4.2). Complete reconfiguration subsequently required.
N E Off
On
Off -