6 x Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
49
6.5 Rotary switch setting: Set Temp Day
Parameter Designation Access Setting range
Min / Max
Factory
setting
Increment
BE HF
T-Room 1 Setpoint Target room temperature for the 1st switching cycle of the timer programmes [Automatic 1]
a
nd [Automatic 2].
E E 5 - 40 °C 20 °C 0,5 °C
T-Room 2 Setpoint Target room temperature for the 2nd switching cycle of the timer programmes [Automatic 1]
a
nd [Automatic 2].
E E 5 - 40 °C 20 °C 0,5 °C
T-Room 3 Setpoint Target room temperature for the 3rd switching cycle of the timer programmes [Automatic 1]
a
nd [Automatic 2].
E E 5 - 40 °C 20 °C 0,5 °C
Tab. 6-7 Parameter in rotary switch setting "Set Temp Day"
6.6 Rotary switch setting: Set Temp Night
Parameter Designation Access Setting range
Min / Max
Factory
setting
Increment
BE HF
T-Reduced Target room temperature for the setback times for the permanent timer programmes
[Automatic 1] and [Automatic 2].
E E 5 - 40°C 15 °C 0,5 °C
T-Absence Target room temperature for the setback times for the temporary timer programmes [Away]
a
nd [Vacation].
E E 5 - 40°C 15 °C 0,5 °C
Tab. 6-8 Parameter in rotary switch setting "Set Temp Night"
6.7 Rotary switch setting: DHW Set Temp
Parameter Designation Access Setting range
Min / Max
Factory
setting
Increment
BE HF
T-DHW Setpoint 1 Target hot water temperature for the 1st switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E E 35 - 70 °C 48 °C 1 °C
T-DHW Setpoint 2 Target hot water temperature for the 2nd switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E E 35 - 70 °C 48 °C 1 °C
T-DHW Setpoint 3 Target hot water temperature for the 3rd switching cycle of the timer programmes
[Automatic 1] and [Automatic 2].
E E 35 - 70 °C 48 °C 1 °C
Tab. 6-9 Parameter in rotary switch setting "DHW Set Temp"