Field Setting from Remote Controller SiUS281811EA
162 Part 5 Field Settings and Test Operation
Note(s)
1.5.20 Ceiling Height Setting, Setting of Normal Airflow
Make the following setting according to the ceiling height. The second code No. is set to 01 at the
factory.
1. The Second Code No. is factory set to Standard/All-direction airflow. For High ceiling (1) or (2),
initial setting by remote controller is required.
2. A closing member kit (optional) is required for 4-, 3-, or 2-direction airflow.
1.5.21 Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material kit of
air discharge outlet has been installed.) The second code No. is factory set to 01.
: Factory setting
FCQ18/24TA : Factory setting
Mode
No.
First
Code
No.
Second
Code No.
Setting
Ceiling Height
All round
outlet
4-way
Outlets
3-way
Outlets
2-way
Outlets
13
(23)
0
01
Standard
Lower than
2.7 m
(8-3/4 ft)
Lower than
3.1 m
(10-1/8 ft)
Lower than
3.0 m
(10 ft)
Lower than
3.5 m
(11-1/2 ft)
02
High Ceiling
(1)
Lower than
3.0 m
(10 ft)
Lower than
3.4 m
(11-1/8 ft)
Lower than
3.3 m
(10-3/4 ft)
Lower than
3.8 m
(12-1/2 ft)
03
High Ceiling
(2)
Lower than
3.5 m
(11-1/2 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
3.5 m
(11-1/2 ft)
FCQ30/36/42/48TA : Factory setting
Mode
No.
First
Code
No.
Second
Code
No.
Setting
Ceiling Height
All round
outlet
4-way
Outlets
3-way
Outlets
2-way
Outlets
13
(23)
0
01
Standard
Lower than
3.2 m
(10-1/2 ft)
Lower than
3.4 m
(11-1/8 ft)
Lower than
3.6 m
(12 ft)
Lower than
4.2 m
(13-3/4 ft)
02
High Ceiling
(1)
Lower than
3.6 m
(12 ft)
Lower than
3.9 m
(12-3/4 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
4.2 m
(13-3/4 ft)
03
High Ceiling
(2)
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.5 m
(14-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
FAQ-TA : Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23) 0
01
Standard
02 A little increase
03 Increase
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23) 1
01
F: 4-direction airflow
02 T: 3-direction airflow
03 W: 2-direction airflow