EasyManua.ls Logo

Daikin SkyAir FHQ24PVJU - Field Settings from Outdoor Unit

Daikin SkyAir FHQ24PVJU
331 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SiUS281811EA Field Setting from Remote Controller
Part 5 Field Settings and Test Operation 163
Note(s)
1.5.22 Swing Pattern Settings
(For units with an infrared floor sensor)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side
by side are set to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
: Factory setting
1.5.23 Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
When the model FCQ-TA is attached with a closing member kit, set the Second Code No. to 02 or
03.
1.5.24 External Static Pressure Settings
Make external static pressure setting automatically using automatic airflow adjustment, or manually
using external static pressure settings.
Make sure that 11 (21)-7 (Airflow adjustment) is set to 01 (OFF).
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23) 2
01 All direction synchronized swing
02
03
Facing swing
FCQ-TA, FAQ-TA : Factory setting
Mode
No.
First Code
No.
Second Code
No.
Contents
13 (23) 4
01 Draft prevention (Upward)
02
Standard
03 Ceiling soiling prevention (Downward)
FBQ-P : Factory setting
Mode No. First Code No. Second Code No. Contents
13 (23) 6
02 50 Pa (0.20 inWG)
03 60 Pa (0.24 inWG)
04 70 Pa (0.28 inWG)
05 80 Pa (0.32 inWG)
06 90 Pa (0.36 inWG)
07
100 Pa (0.40 inWG)
08 110 Pa (0.44 inWG)
09 120 Pa (0.48 inWG)
10 130 Pa (0.52 inWG)
11 140 Pa (0.56 inWG)
12 150 Pa (0.60 inWG)
13 160 Pa (0.64 inWG)
14 180 Pa (0.72 inWG)
15 200 Pa (0.80 inWG)

Table of Contents

Other manuals for Daikin SkyAir FHQ24PVJU

Related product manuals