The numbers in the No. column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory setting
1
Cool / heat
unified address
khhhhhk
Address 0
khhhhhh
Binary number 1
khhhhhk
~)stigid 6(
31
khkkkkk
2
Low noise / demand
address
khhhhkh
Address 0
khhhhhh
Binary number 1
khhhhhk
~ )stigid 6(
31
khkkkkk
3 Test operation settings
khhhhkk
Test operation : OFF
khhhhhk
Test operation : ON
khhhhkh
5 Indoor unit forced fan H
khhhkhk
Normal operation
khhhhhk
Indoor forced fan H
khhhhkh
6
Indoor unit forced
operation
khhhkkh
Normal operation
khhhhhk
Indoor forced operation
khhhhkh
8Te setting
khhkhhh
Target Te: 11°C (51.8°F)
khhhkkk
10°C (50°F)
khhhkkh
9°C (48.2°F)
khhhkhk
8°C (46.4°F)
khhhkhh
Variable (VRT)
khhhhkk
6°C (42.8°F)
khhhhkh
3°C (37.4°F)
khhhhhk
9Tc setting
khhkhhk
Target Tc: 52°C (125.6°F)
khhhkhh
46°C (114.8°F)
khhhhkh
Variable (VRT)
khhhhhk
10
Defrost changeover
setting
khhkhkh
Earlier start defrost
khhhkhh
Normal (factory setting)
khhhhkh
Later start defrost
khhhhhk
12
External low noise /
demand setting
khhkkhh
External low noise/demand:
NO
khhhhhk
External low noise/demand:
YES
khhhhkh
13 AIRNET address
khhkkhk
Address 0
khhhhhh
Binary number 1
khhhhhk
~ )stigid 6(
63
kkkkkkk
16
Setting of heat pump
lockout 1
khkhhhh
OFF
khhhhhk
ON
khhhhkh
19
Emergency automatic
heat pump lockout
khkhhkk
OFF
khhhhhk
ON
khhhhhh
20
Additional refrigerant
charge operation setting
khkhkhh
Refrigerant charging: OFF
khhhhhk
Refrigerant charging: ON
khhhhkh
21
Refrigerant recovery /
vacuuming mode setting
khkhkhk
Refrigerant recovery /
vacuuming: OFF
khhhhhk
Refrigerant recovery /
vacuuming: ON
khhhhkh
22
Night-time low noise
setting
khkhkkh
OFF
khhhhhh
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh
Level 3 (outdoor fan with 4 step or lower)
khhhhkk