The numbers in the No. column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory setting
25 Setting of low noise level
khkkhhk
Level 1 (outdoor fan with 6 step or lower)
khhhhhk
Level 2 (outdoor fan with 5 step or lower)
khhhhkh ∗
Level 3 (outdoor fan with 4 step or lower)
khhhkhh
26
Night-time low noise
operation start setting
khkkhkh
About 8:00 PM
khhhhhk
About 10:00 PM (factory setting)
khhhhkh ∗
About 12:00 AM
khhhkhh
27
Night-time low noise
operation end setting
khkkhkk
About 6:00 AM
khhhhhk
About 7:00 AM
khhhhkh
About 8:00 AM (factory setting)
khhhkhh ∗
28
Power transistor check
mode
khkkkhh
OFF
khhhhhk ∗
ON
khhhhkh
29
Capacity precedence
setting
khkkkhk
OFF
khhhhhk ∗
ON
khhhhkh
30 Demand setting 1
khkkkkh
60 % demand
khhhhhk
70 % demand
khhhhkh ∗
80 % demand
khhhkhh
32 Constant demand setting
kkhhhhh
OFF
khhhhhk ∗
ON
khhhhkh
37
Setting of heat pump
lockout 2
kkhhkhk
OFF
khhhhhh ∗
Mode 1
khhhhhk
Mode 2
khhhhkh
Mode 3
khhhhkk
Mode 4
khhhkhh
Mode 5
khhhkhk
Mode 6
khhhkkh
41 Cooling comfort setting
kkhkhhk
Eco
khhhhhh
Mild
khhhhhk ∗
Quick
khhhhkh
Powerful
khhhkhk
42 Heating comfort setting
kkhkhkh
Eco
khhhhhh
Mild
khhhhhk ∗
Quick
khhhhkh
Powerful
khhhkhk
47
Heat pump lockout
release differential
kkhkkkk
2.8°C (5°F)
khhhhhh
5.6°C (10°F)
khhhhhk ∗
8.3°C (15°F)
khhhhkh