Field Settings from Outdoor Unit SiUS281811EA
176 Part 5 Field Settings and Test Operation
The numbers in the No. column represent the number of times to press the SET (BS2) button.
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
Factory setting
50
Auxiliary heater
maximum allowable
temperature
kkkhhkh
–17.7°C (0°F)
khhhhhh
–15°C (5°F)
khhhhhk
–12.2°C (10°F)
khhhhkh
–9.4°C (15°F)
khhhhkk
–6.6°C (20°F)
khhhkhh
–3.8°C (25°F)
khhhkhk
–1.1°C (30°F)
khhhkkh
1.6°C (35°F)
khhhkkk
4.4°C (40°F)
khhkhhh
7.2°C (45°F)
khhkhhk
10°C (50°F)
khhkhkh
12.7°C (55°F)
khhkhkk
15.5°C (60°F)
khhkkhh
18.3°C (65°F)
khhkkhk
Auxiliary heater always not allowed
khhkkkh
Auxiliary heater always allowed
khhkkkk
56
Auxiliary heater
maximum allowable
temperature release
differential
kkkkhhh
2.8°C (5°F)
khhhhhh
5.6°C (10°F)
khhhhhk
8.3°C (15°F)
khhhhkh
57
Heat pump lockout
temperature
kkkkhhk
–26.1°C (–15°F)
khhhhhh
–23.3°C (–10°F)
khhhhhk
–20.5°C (–5°F)
khhhhkh
–17.7°C (0°F)
khhhhkk
–15°C (5°F)
khhhkhh
–12.2°C (10°F)
khhhkhk
–9.4°C (15°F)
khhhkkh
–6.6°C (20°F)
khhhkkk
–3.8°C (25°F)
khhkhhh
–1.1°C (30°F)
khhkhhk
1.6°C (35°F)
khhkhkh
4.4°C (40°F)
khhkhkk
7.2°C (45°F)
khhkkhh
10°C (50°F)
khhkkhk
Forced heat pump lockout
khhkkkh