INFORMATION
All thermistors have a resistance tolerance of 3%.
INFORMATION
In most cases, the user interface allows to monitor the thermistors.
If the measured resistance value matches the resistance determined through the
measured temperature, but the temperature for the corresponding thermistor is
NOT correct on the user interface display, replace the applicable PCB.
Does the measured resistance of the
thermistor match with the
temperature determined resistance?
Action
Yes Thermistor is OK. Return to the
troubleshooting of the specific error
and continue with the next procedure.
No Replace the specific thermistor, see
"Repair procedures"[4122].
Repair procedures
To remove the thermistor
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
Prerequisite: Remove the required plate work, see "2.13Plate work"[499].
1 Locate the thermistor that needs to be removed.
2 Cut the tie straps that fix the insulation and the thermistor wire.