ESIE18-03C – 2020.02
T °C T °C T °C T °C
–19
–18
–17
–16
–15
–14
–13
–12
–11
186.53
175.97
166.07
156.80
148.10
139.94
132.28
125.09
118.34
11
12
13
14
15
16
17
18
19
38.08
36.30
34.62
33.02
31.50
30.06
28.70
27.41
26.18
41
42
43
44
45
46
47
48
49
10.21
9.81
9.42
9.06
8.71
8.37
8.05
7.75
7.46
71
72
73
74
75
76
77
78
79
3.32
3.21
3.11
3.01
2.91
2.82
2.72
2.64
2.55
–10 111.99 20 25.01 50 7.18 80 2.47
–9
–8
–7
–6
–5
–4
–3
–2
–1
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
21
22
23
24
25
26
27
28
29
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
51
52
53
54
55
56
57
58
59
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
0 65.84 30 16.10 60 4.87
1
2
3
4
5
6
7
8
9
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
31
32
33
34
35
36
37
38
39
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
61
62
63
64
65
66
67
68
69
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
4 Measure the resistance between the appropriate connection points of the
thermistor.
5 Check that the measured resistance value matches the resistance determined
through the measured temperature (earlier step in the procedure). E.g:
Measured temperature with contact thermometer: 23.1°C,
Resistance value determined through temperature (using the table for type
1 thermistors):
Resistance at 20°C: 24.3kΩ,
Resistance at 25°C: 19.4kΩ,
Measure resistance between pin 1‑2:
Measured resistance: 21.86kΩ,
Measured resistance value is inside the range. Thermistor passes the check.