SiE-05C Test Operation
Test Operation Inverter K Series 107
Wiring for Indoor
Unit
Terminals F1 and F2 of the unified ON/OFF controllers terminal block for control and terminals F1 and F2
of the indoor unit with set group No. are wired as shown in the figure below. (There is no polarity, so it
doesnt matter if F1 and F2 are inverted.)
1: Forced OFF input (T1, T2)
All connected indoor units go off and do not run while forced OFF input (for no-voltage contact, micro-
current) is closed. Use a contact that can guarantee a 16 VDC, 10 mA minimum applicable load.
NOTE: If using an instantaneous contactor, use one that handles conducting time of 200 msec or more.
2: Power supply for schedule timer (D1, D2)
Wire only if 1, 2 and 3 are used.