SiE-05C Functions
Functions Inverter K Series 47
1.17 Oil Temperature Sensor (8 and 10 Hp only)
1.17.1 Prevention of Wetness During Heating
Wet operation is prevented by modification of super heating (SH) by oil temperature sensor (R5T).
(Low equivalent pressure = Te)
1.17.2 Prevention of Oil Dilution During Defrost
<For products produced before July ’99>
The unit controls upper limit frequency of the compressor and is designed to prevent oil from being
diluted while defrosting by means of an oil temperature sensor.
Startup subsequent to defrosting is improved by the oil temperature sensor.
<For products produced after Aug. ‘99>
The unit controls upper limit frequency of the compressor and is designed to prevent oil from being
diluted while defrosting by means of an oil temperature sensor.
Startup subsequent to defrosting is improved by the oil temperature sensor.
R5T Te+10˚C
SH=10˚C
R5T > Te+10˚C
SH=5˚C
(VF010)
R5T Te+10˚C
INV · 86Hz+STD · ON
R5T > Te+10˚C
INV · 116Hz+STD · ON
(VF011)
R5T Te+10˚C
INV · 116Hz+STD · OFF (20 min.)
R5T > Te+10˚C
Upper limit release
(VF010)
R5T Te+10˚C
INV · 86Hz+STD · ON
R5T > Te+10˚C
INV · 116Hz+STD · ON
(VF083)
R5T Te+10˚C
INV · 116Hz+STD · OFF (20 min.)
R5T > Te+10˚C
Upper limit release
(VF013)
106Hz+OFF
116Hz+ON
Ta < -12˚C
Ta > -10˚C