Troubleshooting SiE-05C
148 Troubleshooting Inverter K Series
3.25 Outdoor Unit: Malfunction of Oil Temperature Thermistor (R5T)
Remote Controller
Display
JJ
JJ
HH
HH
Supposed Causes Defect of oil temperature thermistor (R5T)
Defect of outdoor unit PC board (A1P)
Troubleshooting
(VF051)
The outdoor
unit type is 8 K or 10K.
Is the connector
is connected to X15A of
the outdoor PC board
(A1P)?
Resistance
is normal when
measured with thermistor
(R5T) disconnected from the
outdoor unit PC board.
(0.6 k~360 k)
Replace outdoor unit PC board (A1P).
Connect the thermistor and and turn on
again.
Replace thermistor (R5T).
Replace outdoor unit PC board (A1P).
YES
YES
YES
NO
NO
NO