SiE-05C Functions
Functions Inverter K Series 45
1.16 Drain Pump Control
1. The drain pump is controlled by the ON/OFF buttons (4 button (1) - (4) given in the figure below).
1.16.1 When the Float Switch is Tripped While the Cooling Thermostat is ON:
1. The objective of residual operation is to completely drain any moisture adhering to the fin of the indoor
unit heat exchanger when the thermostat goes off during cooling operation.
2. One cycle consists of 5 minutes of operation, 5 seconds stop, and another 5 minutes of operation.
1.16.2 When the Float Switch is Tripped During Cooling OFF by Thermostat: