Outline of Control SiE-05C
222 Functions PLUS Series
4.1.3 Heating Pump Down Start (For Heat Pump System)
When starting within 3 hours after the compressor stops and pump down residual operation has been
executed before the compressor was stopped, after completing soft start, compressor operating frequency
is held to (60 Hz + OFF) ~ (96 Hz + OFF), the heat exchange pressure equalizing piping solenoid for
standard types 1 and 2 is opened, and the refrigerant in the accumulator of the inverter type is discharged.
The frequency is further maintained at (30 Hz + OFF) for 1 minute, refrigerant in outdoor unit heat
exchangers is evaporated by shutting off hot gas, and operation switches to normal control.
4.1.4 Heating Power on Start (For Heat Pump System)
Discharge refrigerant collected in the low pressure side to protect the compressor when starting for the first
time within 6 hours after turning off the power.
After completing soft start, compressor operating frequency is held to (60 Hz + OFF) ~ (96 Hz + OFF).
After the refrigerant in the pressure equalizing line and accumulator of the inverter type is discharged, the
standard compressors start in sequence, and refrigerant is discharged from each respective low pressure
line.
Indoor unit hot start during this time
Soft start
1 minute elapses
Liquid discharged
from accumulators of
all INV outdoor unit
5 minutes elapse
High pressure > 14k
or or
2 minutes elapse
Low pressure < 1k
1 minute elapses
High pressure
differential of INV
outdoor unit reduced
Refrigerant
discharged from
heat exchangers
Normal control
Initial aperture of EEV = 150 PLS
Compressor frequency limit
EEV of all outdoor units closed
Hot gas bypass On with LP < 0.5k
30 Hz + OFF maintained
Hot gas bypass OFF
after 30 sec.
Compressor P1 control
EEV = 0 PLS
(k:kg/cm
2
)
(VF104)
Compressor frequency
change during control
Low pressure
Min. 1.2 k
continues
for 30 sec.
Min. 1.1 k
continues
for 30 sec.
Min. 1.0 k
continues
for 30 sec.
0.9k
0.8k
0.7k
9 6 Hz
8 6 Hz
7 6 Hz
6 0 Hz
INV compressor frequency limit
EEV for all outdoor units = 0 PLS
Hot gas bypass ON for all outdoor units
Fan H + ON for inverter compressor
INV compressor frequency limit
Start of INV outdoor unit EEV
superheating aperture control
STD outdoor unit 1 EEV = 2000 PLS
Hot gas bypass ON for all outdoor units
STD outdoor unit 1 fan H + ON
INV compressor frequency limit
STD compressor ON + OFF
Start of STD outdoor unit 1
superheating aperture control
Hot gas bypass ON for all outdoor units
INV compressor frequency limit
STD outdoor unit 2 EEV = 0 PLS
Start of indoor unit hot start
Start from 38 Hz + OFF
Liquid discharged
from accumulator
of STD outdoor
unit 1
Low pressure
line of STD
outdoor unit 2 is
opened.
Normal control
15 minutes elapse
High pressure > 16k
Min. 5 min. discharge
Superheating temp.> 30˚C
10 minutes elapse
High pressure > 16k
INV compressor frequency limit
STD outdoor unit 1 EEV = 0 PLS
STD outdoor unit 2 EEV = 2000 PLS
Hot gas bypass ON for all outdoor units
Fan H + ON for all outdoor units
Soft start
1 minute elapses
Liquid
discharged from
accumulators of
INV outdoor unit
Liquid
discharged from
heat exchanger
of STD outdoor
unit 1
Liquid
discharged from
heat exchanger
and low pressure
section of STD
outdoor unit 1
5 minutes elapses
High pressure > 16k
3 minutes elapses
High pressure > 16k
Same as heating pump down control
Compressor frequency
change during control
or
or
or
or
(k:kg/cm
2
)
(VF105)
SI-05C.BOOK Page 222 Monday, November 6, 2000 4:13 PM