SiE-05C Test Operation
Test Operation Inverter K Series 89
1.15 Remote Controller Self-Diagnosis Function
The remote controller switches are equipped with a self diagnosis function so that more appropriate
maintenance can be carried out. If a malfunction occurs during operation, the operation lamp, malfunction
code and display of malfunctioning unit No. let you know the contents and location of the malfunction.
When there is a stop due to malfunction, the contents of the malfunction given below can be diagnosed by
a combination of operation lamp, INSPECTION display of the liquid crystal display and display of
malfunction code. It also lets you know the unit No. during group control.
Operation lamp Inspection display Unit No. Malfunction code Malfunction contents
Blinking Blinking Blinking A0 Indoor unit: Error of external protection device
Blinking Blinking Blinking A1 Indoor unit: Failure of PC board
On Off Blinking A1 Indoor unit: Failure of PC board
Blinking Blinking Blinking A3 Indoor unit: Malfunction of drain level control system (33H)
Blinking Blinking Blinking A6 Indoor unit: Fan motor lock
On Off Blinking A7 Indoor unit: Malfunction of swing flap motor (M1S)
Blinking Blinking Blinking A9 Indoor unit: Malfunction of moving part of electronic
expansion valve (Y1E)
On Off Blinking AF Indoor unit: Drain level above limit
Blinking Blinking Blinking AH Indoor unit: Malfunction of air filter maintenance
Blinking Blinking Blinking AJ Indoor unit: Malfunction of capacity setting
Blinking Blinking Blinking C4 Indoor unit: Malfunction of thermistor (R2T) for liquid pipe
(loose connection, disconnection, short circuit, failure)
Blinking Blinking Blinking C5 Indoor unit: Malfunction of thermistor (R3T) for gas pipes
(loose connection, disconnection, short circuit, failure)
Blinking Blinking Blinking C9 Indoor unit: Malfunction of thermistor (R1T) for air inlet
(loose connection, disconnection, short circuit, failure)
On On On CJ Indoor unit: Malfunction of thermostat sensor in remote
controller
Blinking Blinking Blinking E0 Outdoor unit: Actuation of safety device
Blinking Blinking Blinking E1 Outdoor unit: PC board failure
On Off Blinking E1 Outdoor unit: PC board failure
Blinking Blinking Blinking E3 Outdoor unit: Actuation of high pressure switch
Blinking Blinking Blinking E4 Outdoor unit: Actuation of low pressure switch
Blinking Blinking Blinking E9 Outdoor unit: Malfunction of moving part of electronic
expansion valve (Y1E)
Blinking Blinking Blinking F3 Outdoor unit: Abnormal discharge pipe temperature
On Off Blinking H3 Outdoor unit: High pressure switch failure
Blinking Blinking Blinking H4 Outdoor unit: Actuation of low pressure switch
Blinking Blinking Blinking H9 Outdoor unit: Malfunction of thermistor (R1T) for outdoor air
(loose connection, disconnection, short circuit, failure)
On Off Blinking H9 Outdoor unit: Malfunction of thermistor (R1T) for outdoor air
(loose connection, disconnection, short circuit, failure)
Blinking Blinking Blinking J1 Outdoor unit: Malfunction of pressure sensor
Blinking Blinking Blinking J3 Outdoor unit: Malfunction of discharge pipe thermistor (R3T)
(loose connection, disconnection, short circuit, failure)
On Off Blinking J3 Outdoor unit: Malfunction of discharge pipe thermistor (R3T)
(loose connection, disconnection, short circuit, failure)
Blinking Blinking Blinking J5 Outdoor unit: Malfunction of thermistor (R4T) for suction
pipe (loose connection, disconnection, short circuit, failure)