Troubleshooting SiE-05C
140 Troubleshooting Inverter K Series
3.15 Outdoor Unit: Actuation of High Pressure Switch
Remote Controller
Display
EE
EE
33
33
Supposed Causes Actuation of outdoor unit high pressure switch
Defect of outdoor unit PC board (A1P)
Instantaneous power failure
Troubleshooting
∗1: Actuation of high pressure switch (HPS)
The outdoor unit PC board’s connector is disconnected.
Is the outdoor unit heat exchanger dirty?
Defect of outdoor fan
Is the refrigerant over-charged?
Operation
is normal when turned on
again by remote
controller.
Replace outdoor unit PC board A1P.
Actuation of high pressure switch ∗1
YES
YES
There was an instantaneous power
failure or a past safety device actuated.
Re-check refrigerant system.
NO
NO
(VF041)
Contact
S1HP (X10A) or S2HP
(X11A) is open.