SiE-05C Functions
Functions Inverter K Series 27
1.3 List of Safety Devices and Functinal Parts Setting Values
1.3.1 Outdoor Unit
RSXY5~10K
Note 1. These parts are for heat pump model only.
2. ∗: For products produced after Aug. ‘99.
Item Symbol Name Type
RSX(Y)5K RSX(Y)8K RSX(Y)10K
Comp-
ressor
Inverter
side Model
Output
Y1 INV JT100BAVYE 3.5 kW JT100BAVTYE 3.5 kW JT100BAVTYE 3.5 kW
STD JT100BATYE 2.2 kW JT160BATYE 3.75kW
YAL INV JT100BAVYE 3.5 kW JT100BAVTYE 3.5 kW JT100BAVTYE 3.5 kW
STD JT100BATYH 2.2 kW JT160BATYH 3.75kW
TAL INV JT100BAV 3.5 kW JT100BAVT 3.5 kW JT100BAVT 3.5 kW
STD JT100BAT 2.2 kW JT160BAT 3.75kW
Compressor safety
thermostat
Discharge pipe thermistor 135˚C OFF
J1HC/
J2HC
Crank case heater 33W 33W+33W
F2C Over-current
relay
Y1 — HOE-20F-TRA1
10A
HOE-20F-TRA1
13A
YAL — HOE-20F-TRA1
10A
HOE-20F-TRA1
13A
TAL — HOE-20-TRA1
15A
HOE-26-TRA1
24A
Safety
device
Q1M
Q2M
Fan motor 190W 140W+230W
Safety thermostat Open 135˚C ± 5˚C 140W: Open 120 ± 5˚C, 230W: 135 ± 5˚C
S1P Pressure switch (for high
pressure safety)
20SP-688-6
OFF: 27.5+0~-1.0kg/cm²
ON: 20.0+1.0~-1.0kg/cm²
—
S1HP Pressure switch (for high
pressure safety)
— 20SP-688-6 OFF: 27.5+0~-1.0kg/cm
2
ON: 20.0+1.0~-1.0kg/cm²
S2HP Pressure switch (for high
pressure safety)
— 20SP-688-6 OFF: 27.5+0~-1.0kg/cm
2
ON: 20.0+1.0~-1.0kg/cm²
Fusible plug FPG-3D 70~75˚C
Sensor SENPH Pressure sensor PS8030A 0~30kg/cm² (0~2.94MPa)
SENPL Pressure sensor PS8030A 0~10kg/cm² (0~0.98MPa)
R1T Thermistor (for outdoor air) 3.5~360KΩ
R2T Thermistor
(for heat exchange)
3.5~360KΩ
R3T Thermistor
(for discharge pipe)
3.5~400KΩ —
R3-1T Thermistor (for inverter
discharge pipe)
— 3.5~400KΩ
R3-2T Thermistor (for standard
discharge pipe)
— 3.5~400KΩ
R4T Thermistor
(for suction pipe)
3.5~360KΩ
R5T Thermistor
for inverter oil temperature)
— 3.5~400KΩ (∗ 3.5~360KΩ)
Other
functions
/parts
Y1E
Note 1
Electronic
expansion valve
When
cooling
ON: 2,000 pulses (completely open); OFF: 0 pulses (completely closed)
When
heating
ON: PI control; OFF: 0 pulses (completely closed)
Y2S Solenoid valve
(for hot gas bypass)
NEV603
Y3S Solenoid valve
(for inverter injection)
NEV202 (∗ ST10D)
Y4S Solenoid valve
(for standard injection)
— NEV202 (∗ ST10D)
Y1S
Note 1
Solenoid valve
(pressure equalizing)
— NEV202 (∗ ST10D)
SI-05C.BOOK Page 27 Monday, November 6, 2000 4:13 PM