Test Operation SiE-05C
72 Test Operation Inverter K Series
1.7 Low Noise / Demand Operation
External control adaptor for outdoor unit is required for each low noise and demand control zone.
By using a separate External control adaptor for outdoor unit and setting the outdoor unit address
(setting mode 2) for each low noise and demand control zone, demand and low noise operation is
carried out in accordance with contact input received from the adaptor in each zone.
Outdoor unit address setting (Setting mode 2; see page 59.)
External control adaptor for outdoor unit address setting
Decide and set demand address 0 - 31 for each demand and low noise control zone. (See fig. below.)
Set SS1 to BOTH (factory set) or C / H.
F1 / F2
Demand address
¡

(F1 / F2)
External control
adaptor for
outdoor unit
F1 / F2 F1 / F2
DS2·DS1
No. 0
F1 / F2 F1 / F2
Demand address
¡

¡
(F1 / F2)
External control
adaptor for
outdoor unit
F1 / F2 F1 / F2
DS2·DS1
No. 1
F1 / F2 F1 / F2
Demand address
¡

¡
(F1 / F2)
External control
adaptor for
outdoor unit
F1 / F2
DS2·DS1
No. 2
(VL030)