SiE-05C Test Operation
Test Operation Inverter K Series 109
Wiring for
Transmission
<Indoor unit wiring>
1. If schedule timer individual use:
For the schedule timers power supply, connect the schedule timers connectors (D1/D2) and the
connector on the indoor units PC board (CN18) with the attached cable and crimp style terminals.
2. If using in combination with other optional controllers for centralized control:
Wiring for transmission: 0.75~1.25 mm² sheathed vinyl cord or cable (double core)....Max. extension
1000 m (Total wiring length 2000 m)
<Connection example of wiring for transmission>
(1)series wiring, (2) bus type wiring and (3) star type wiring are the same as with a central remote
controller.
SI-05C.BOOK Page 109 Monday, November 6, 2000 4:13 PM