Troubleshooting (OP: Schedule Timer) SiE-05C
176 Troubleshooting Inverter K Series
7.5 Address Duplication, Improper Setting
Remote Controller
Display
MM
MM
CC
CC
Supposed Causes Address duplication of optional controller for centralized control
Troubleshooting
(VF078)
Are two or more
schedule timers
connected?
Reset the power supply for the
schedule timer.
Disconnect all schedule timers except
one and reset the schedule timer's
power supply.
YES
NO
SI-05C.BOOK Page 176 Monday, November 6, 2000 4:13 PM
Все каталоги и инструкции здесь: http://splitoff.ru/tehn-doc.html