Troubleshooting SiE-05C
302 Troubleshooting PLUS Series
3.2 Outdoor Unit: Actuation of Safety Device
Remote Controller
Display
EE
EE
00
00
Applicable Models HWL of constant speed outdoor Unit is lit
Supposed Causes Tripped outdoor unit safety device (INV outdoor unit / constant speed outdoor unit)
Faulty outdoor unit PC board (INV outdoor unit / constant speed outdoor unit)
Instantaneous power failure
Troubleshooting
∗1: Magnetic switch OC
Faulty compressor
Power supply voltage malfunction
Faulty magnetic switch
Other
∗2: Tripped fan motor safety thermostat
Faulty fan motor
Faulty condenser
Other
YES
YES
YES
YES
Connect the connectors or
terminals and operate.
Standard 1 type unit
magnetic switch OC ∗1
Standard 2 type unit
magnetic switch OC ∗1
Tripped fan motor safety
thermostat ∗2
There was an instantaneous
power failure or a safety
device was tripped. Check
the refrigerant system again.
Outdoor unit PC board (A1P)
exchange
The F1C (X1S - X2S)
contact is open.
Connectors
or terminals are
connected to X8A - X11A and
X1S - X4S of the outdoor
unit PC board
(A1P).
The F2C (X3S-X4S)
contact is open.
Operates normally
when operated by remote
controller.
NO
NO
NO
NO
YESThe Q1M (X8A) or
Q2M (X9A) contact
is open.
NO
(VF137)