SiE-05C Troubleshooting
Troubleshooting PLUS Series 319
3.23 Refrigerant System not set, Incompatible Wiring/Piping
Remote Controller
Display
UU
UU
FF
FF
Supposed Causes Improper connection of transmission wiring between indoor unit and outdoor unit, or outdoor and
outdoor unit
Failure to execute wiring check operation
Defect of indoor unit PC board
Troubleshooting
Wiring check may not be successful if carried out after the outdoor unit has been off for more than 12
hours, or if it is not carried out after running all connected indoor units in the fan mode for at least an hour.
Wiring check operation
carried out?
Is indoor-outdoor
and outdoor-outdoor unit
transmission wiring
normal?
YES
NO
NO
Is indoor-outdoor
and outdoor-outdoor unit
transmission wiring
normal?
YES
YES
NO
Replace indoor unit PC board.
After fixing incorrect wiring, push
and hold the RESET button on the
outdoor unit PC board for 5
seconds.
The unit will not run for up to 12
minutes.
Wiring check may not have been
carried out successfully.
(VF157)
SI-05C.BOOK Page 319 Monday, November 6, 2000 4:13 PM