SiE-05C Backup and Emergency Operation
Special Service Mode PLUS Series 333
Malfunctions for
which Backup
Operation can or
cannot Be
Executed
Malfunction Malfunction Code PC Board Type
EB9446~9A EB9446~9B (Applies to items
manufactured from June on.)
Tripped Safety Device E0 Cannot Operate Can Operate
Faulty PC Board E1 Cannot Operate Cannot Operate
Tripped LPS E4 Cannot Operate Can Operate
Solenoid Valve Malfunction E9 Cannot Operate Can Operate
Discharge Pipe
Temperature Malfunction
F3 Cannot Operate Can Operate
Faulty Control HPS H3 Cannot Operate Cannot Operate
Faulty Control LPS H4 Cannot Operate Cannot Operate
Air Thermistor Malfunction H9 Can Operate Can Operate
Discharge Pipe Thermistor
Malfunction
J3 Cannot Operate Can Operate
Suction Pipe Thermistor
Malfunction
J5 Can Operate Can Operate
Heat Exchange Thermistor
Malfunction
J6 Can Operate Can Operate
Oil Temperature Thermistor
Malfunction
JH Can Operate Can Operate
Header Thermistor
Malfunction
J7 Can Operate Can Operate
Reverse Phase / Negative
Phase
U1 Cannot Operate Cannot Operate
Outdoor - L Transmission
Malfunction
U7 Cannot Operate Cannot Operate
SI-05C.BOOK Page 333 Monday, November 6, 2000 4:13 PM