Wiring Adaptor SiE-05C
382 Appendix Inverter K Series / PLUS Series
Input for Monitoring Wire according to the following procedure depending on whether input is voltage or no voltage.
For voltage input:
Set the voltage / no voltage changeover switch (SS1) to voltage. (Factory set setting complete)
For no voltage input:
Set the voltage / no voltage changeover switch (SS1) to no voltage.
If you want to connect output which is to be ON when apparatus is operating normally, disconnect the
short circuit wire between B1 and BC and connect output of the apparatus here.
Connect output which is to be ON when apparatus is malfunctioning between B2 and BC. (You can
fetch stop malfunction in the case of stop malfunction.)
When operating from optional controllers for centralized control, if between B2 and BC is ON or stop
malfunction with / without switch (SS3) is set to with, in the case of between B1 - BC being ON,
optional controllers for centralized control display a malfunction (malfunction code A1).
After switching from OFF to ON with an optional controller for centralized control, it takes 10 - 30 for the
monitor to display a malfunction.
Individual
Changeover Switch
(SS2)
Switch for toggling between individual mode and dedicated central mode (stop cannot be effected from
other air conditioner).
For without individual, stop can be effected from optional central controller only.
For with individual, stop can be effected from other air conditioner as well.
(Factory set is without individual.)
Malfunction Signal
Switch (SS3)
Switch for carrying out malfunction detection for stop operation from optional central controller.
In the case of with stop malfunction, if operation concerning stop does not follow, the optional central
controller carries out display of malfunction.
In the case of without stop malfunction, even if operation concerning stop does not follow, the optional
central controller does not carry out display of malfunction.
(If SS2 is set to with last command priority, this switch becomes inoperable.)
(Factory set is without stop malfunction.)
Output Changeover
Switch (SS4)
Switch for toggling relay output between constant and instantaneous.
(Factory set is instantaneous.)
Display of optional controllers for centralized control that make monitor input status by combination of
various switches
Setting Individual Stop
malfunction
Central display when there is an ON instruction from
optional controller for centralized control
Combination With ON input Without ON input With malfunction input
1 With With ON OFF Malfunction
2 Without
3 Without With ON Malfunction Malfunction
4 Without ON ON Malfunction
SI-05C.BOOK Page 382 Monday, November 6, 2000 4:13 PM