Functions SiE-05C
34 Functions Inverter K Series
Outdoor Unit
Function
Notes Compressor upper limit is 116Hz+OFF for 10 minutes of next start after entering residual operation.
(∗ Except for products produced after Aug. ‘99.)
During defrost or oil return, residual operation is not carried out even if a stop command comes.
Forced thermostat OFF occurs if defrost or oil return signal comes during residual operation.
Outdoor air (R1T) Compressor Electronic
expansion valve
Pressure equalizing
solenoid valve
Time
INV STD
R1T < -10˚C 86Hz OFF 0~300 pulses ON or OFF 10 min.
-10˚C ≤ R1T < 0˚C 76Hz OFF 0~300 pulses ON or OFF 10 min.
R1T ≥ 0˚C 60Hz OFF 0~300 pulses ON or OFF 10 min.