Functions SiE-05C
38 Functions Inverter K Series
Low Outdoor Air
Cooling IN
Conditions (Step 2)
<For products produced after Aug. ’99>
Normal operation
Step 2
• Cooling with compressor running
(doesn't include oil return)
&
• High pressure < 7.5 kg/cm²
(0.735 MPa)
&
• Outdoor air temperature < 20˚C
&
• Radiator fin temperature < 60˚C
• Compressor off
or
•
Other than cooling (includes oil return)
or
• High pressure > 15.8 kg/cm²
(1.548 MPa)
or
• Outdoor air temperature > 25˚C
or
• Radiator fin temperature > 80˚C
Condition satisfied
Conditions satisfied
(VF007-1)
Normal operation
Step 2
• Cooling with compressor running
(doesn't include oil return)
&
• High pressure < 7.5 kg/cm²
(0.735 MPa)
&
• Radiator fin temperature < 60˚C
• Compressor off
or
•
Other than cooling (includes oil return)
or
• High pressure > 15.8 kg/cm²
(1.548 MPa)
or
• Radiator fin temperature > 80˚C
Condition satisfied
Conditions satisfied
(VF007-2)
SI-05C.BOOK Page 38 Monday, November 6, 2000 4:13 PM