Test Operation SiE-05C
60 Test Operation Inverter K Series
Emergency operation
Normal operation
No Setting item Description LED display
H1P H2P H3P H4P H5P H6P H7P
Emergency
operation when
malfunction
occurs
EMG
1
1
LED display
H1P H2P H3P H4P H5P H6P H7P
LED display
H1P H2P H3P H4P H5P H6P H7P
Initial setting (EMG)
Initial setting (EMG)
S
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
S
S
S
S
S
S
S
S
S
S
S
S
S
Forced fan operation
(H tap)
Normal operation
Fan of stopped
indoor unit turns
Forced fan
switch
4
S
Forced fan operation
(H tap)
Normal operation
Allows operation
of indoor unit
from outdoor unit
Indoor unit
forced
operation
5
S
Frequency fix
Normal operation
Fixes the
frequency of the
inverter
compressor
5HP···68Hz
8.10HP···
86Hz+ON
Frequency
fix
6
S
Address 0
Binary number 1
(6 digits) 2
31
Address for
cool/heat group
operation
Cool/heat
group
address
2
S
S
S
S
Address 0
Binary number 1
(6 digits) 2
63
Airnet addressNot used10
S
S
S
S
Address 0
Binary number 1
(6 digits) 2
31
Address for low
noise / demand
group operation
Low noise /
demand
address
3
S
S
S
High
Normal (factory set)
Low
Low pressure
setting for cooling
Te setting7
High pressure
setting for
heating
Tc setting8
S
S
S
Quick defrost
Normal (factory set)
Slow defrost
Temperature
setting for defrost
Defrost
setting
9
S
R
S