Test Operation SiE-05C
70 Test Operation Inverter K Series
Supplement Supplement to 1.6.3 and 1.6.4
If using several adaptor PCB and you want to select cool/heat mode for each adaptor PCB, set DS1 / DS2
of the adaptor PCB and the cool/heat group address on the outside units PCB to the same setting in
setting mode 2.
Adaptor
PCB
No. 0
Outdoor unit
group master
No. 0
Outdoor unit
group slave
No. 0
Outdoor unit
group slave
No. 0
Cool/heat group address
¡

DS2·DS1
Adaptor
PCB
No. 1
Outdoor unit
group master
No. 1
Outdoor unit
group slave
No. 1
Cool/heat group address
¡

¡
DS2·DS1
Adapter
PCB
No. 2
Outdoor unit
group master
No. 2
Outdoor unit
group slave
No. 2
Outdoor unit
group slave
No. 2
Cool/heat group address
¡

¡
DS2·DS1
Adapter
PCB
No. 3
Outdoor unit
group master
No. 3
Outdoor unit
group slave
No. 3
Cool/heat group address
¡

¡¡
DS2·DS1
(VL028)
SI-05C.BOOK Page 70 Monday, November 6, 2000 4:13 PM