6 Application Set-Up Examples
6.1 Introduction
NOTE
When
the optional safe
stop feature is used, a jumper wire
may be required between terminal 12 (or 13) and terminal
37 for the frequency converter to operate when using
factory default programming values.
The examples in this section are intended as a quick
reference for common applications.
•
Parameter settings are the regional default values
unless otherwise indicated (selected in
0-03 Regional Settings)
•
Parameters associated with the terminals and
their settings are shown next to the drawings
•
Where switch settings for analog terminals A53 or
A54 are required, these are also shown
6.2 Application Examples
Parameters
Function Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal
53
High Voltage
10 V*
6-14 Terminal
53
Low Ref./Feedb.
Value
0 Hz
6-15 Terminal
53
High Ref./Feedb.
Value
50 Hz
* =
Default Value
Notes/comments:
D
IN 37 is
an option.
Table 6.3 Analog Speed Reference (Voltage)
Application Set-Up Examples
VLT
®
HVAC Drive Operating Instructions
MG11AI02 - VLT
®
is a registered Danfoss trademark
47
6 6