Wiring
Table 6: Wiring details
AI1 - AI5
Temperature inputs
S3, S4, S5, S7, S8
Pt 1000 AKS11, PTC 1000 EKS111, NTC5K EKS211, NTC10K EKS221 or a user-dened sensor type. All have to be of the same type.
S3, air sensor, placed in the warm air before the evaporator
S4, discharge air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be selected in the conguration)
S5, defrost sensor, placed in the evaporator
S7, Brine inlet, placed at the inlet of the water cooled condenser
S8, Brine outlet, placed at the outlet of the water cooled condenser
(If the S8 sensor is in use, DI1 input will appear as AI5.)
DI1
Digital input signal
The dened function is active when the input is short-circuited or opened, depending on the function dened in o02.
DI2
Digital input signal
The dened function is active when the input is short-circuited or opened, depending on the function dened in o37.
AO1
In application mode 1-4 the output can be used to drive an external high-powered solid-state relay for fast pulsing of rail heat
In application 5 and 6 the output is used for speed control of compressor
In application 7 and 8 the output is used for speed control of a brine pump
The following output signals are supported:
0 – 10 V DC
Frequency
Pulse Width Modulation (PWM)
MODBUS
For data communication.
Terminal 83 = B-
Terminal 84 = A+
Terminal 85 = screen
Supply voltage
230 V AC or 115 V AC
DO1
Compressor or brine pump:
There is connection between terminal 8 and 9 when the compressor/brine pump is ON.
DO2
Alarm:
There is a connection between terminal 10 and 12 in alarm situations and when the controller is without power.
DO3
Fan:
There is connection between terminal 13 and 14 when the fan is ON.
DO4
Light or compressor 2:
There is connection between terminal 15 and 16 when compressor 2 is ON.
There is connection between terminal 15 and 17 when light is ON.
DO5
Defrost:
There is connection between terminal 18 and 19 when defrosting takes place.
Application 2 / 4 / 6
and 8
Here, the free outputs can be user dened for one of the following functions:
Fan
Fan ECO
Defrost
Rail heat
Alarm
Light
Night blinds
Air heater
Condenser fan
Display (RJ12 plug)
If readings/operation of the controller is required, an external display can be connected.
The max. cable length is 100 m.
Electric noise
Cables for sensors, low voltage DI inputs and data communication must be kept separate from other electric cables:
Use separate cable trays
Keep a distance between cables of at least 10 cm
Long cables at the low voltage DI input should be avoided
Installation considerations
Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and
ultimately lead to a plant breakdown.