Wiring
Table 6: Wiring details
Temperature inputs
• S3, S4, S5, S7, S8
Pt 1000 AKS11, PTC 1000 EKS111, NTC5K EKS211, NTC10K EKS221 or a user-dened sensor type. All have to be of the same type.
• S3, air sensor, placed in the warm air before the evaporator
• S4, discharge air sensor, placed in the cold air after the evaporator
(the need for either S3 or S4 can be selected in the conguration)
• S5, defrost sensor, placed in the evaporator
•
S7, Brine inlet, placed at the inlet of the water cooled condenser
• S8, Brine outlet, placed at the outlet of the water cooled condenser
(If the S8 sensor is in use, DI1 input will appear as AI5.)
Digital input signal
The dened function is active when the input is short-circuited or opened, depending on the function dened in o02.
Digital input signal
The dened function is active when the input is short-circuited or opened, depending on the function dened in o37.
• In application mode 1-4 the output can be used to drive an external high-powered solid-state relay for fast pulsing of rail heat
• In application 5 and 6 the output is used for speed control of compressor
• In application 7 and 8 the output is used for speed control of a brine pump
The following output signals are supported:
• 0 – 10 V DC
• Frequency
• Pulse Width Modulation (PWM)
For data communication.
• Terminal 83 = B-
• Terminal 84 = A+
• Terminal 85 = screen
Compressor or brine pump:
There is connection between terminal 8 and 9 when the compressor/brine pump is ON.
Alarm:
There is a connection between terminal 10 and 12 in alarm situations and when the controller is without power.
Fan:
There is connection between terminal 13 and 14 when the fan is ON.
Light or compressor 2:
There is connection between terminal 15 and 16 when compressor 2 is ON.
There is connection between terminal 15 and 17 when light is ON.
Defrost:
There is connection between terminal 18 and 19 when defrosting takes place.
Application 2 / 4 / 6
and 8
Here, the free outputs can be user dened for one of the following functions:
• Fan
• Fan ECO
• Defrost
•
Rail heat
• Alarm
• Light
•
Night blinds
•
Air heater
•
Condenser fan
Display (RJ12 plug)
If readings/operation of the controller is required, an external display can be connected.
The max. cable length is 100 m.
Electric noise
Cables for sensors, low voltage DI inputs and data communication must be kept separate from other electric cables:
• Use separate cable trays
• Keep a distance between cables of at least 10 cm
• Long cables at the low voltage DI input should be avoided
Installation considerations
Accidental damage, poor installation, or site conditions, can give rise to malfunctions of the control system, and
ultimately lead to a plant breakdown.
Every possible safeguard is incorporated into our products to prevent this. However, a wrong installation could still
present problems. Electronic controls are no substitute for normal, good engineering practice.