Amplication factor Kp for PI control of speed
Integration factor Tn for PI control of speed
Max. Kp value at high deviation from the temperature
setpoint
Thermostat ON time at thermostat sensor error
Thermostat OFF time at thermostat sensor error
The xed speed during emergency control due to an
error on the thermostat sensor
Set the speed at which the compressor will run during
an oil return cycle
Set the time period for which the compressor will run
at increased speed during an oil return cycle
If the compressor is running below the set speed lim-
it, an oil return counter is increased. When the coun-
ter reaches the dened "Oil return cycle time", an oil
return cycle will be initiated
When the counter for low speed operation reaches
this value, an oil return cycle is initiated
Variable speed level at which the resonance band
starts
Width of the resonance band
Condenser control
Table 26: Condenser control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 17=Door open, 18=Melt
period, 19=Modulating temp. control, 20=Emergency
control, 25=Manual control, 29=Case cleaning,
30=Forced cooling, 32=Power-up delay, 33=Air heat-
ing, 34=Comp. safety cut-out, 45=Shut down control-
ler, 50=High S7 Brine inlet
Actual status of output function
Max. temperature safety limit for the condenser en-
tering brine temperature. If the limit is violated, the
compressor capacity will be reduced and an alarm
will be activated. If the temperature decreases with
the set dierential, the alarm will be deactivated
again and the compressor capacity will no longer be
restricted.
Temperature dierential for the safety limit "Max. S7
Brine temp.". If the max. temperature safety limit for
the condenser entering brine temperature is violated,
the compressor capacity will be reduced and an alarm
will be activated. If the temperature decreases with
the set dierential, the alarm will be deactivated
again and the compressor capacity will no longer be
restricted.
Temperature setting at which the condenser fan is
started
Temperature dierential for stopping condenser fan