Function
Description
Values
Code
Short name
MC Defrost start
Master control signal for starting a defrost. At adap-
tive defrost the defrost might be skipped if the de-
frost is not needed.
0=OFF, 1=ON
x13
--- MC def.start
MC Defrost state
Read out the actual state of the defrost
0=OFF, 1=ON
x14
--- DefrostState
MC Hold after de-
frost
Master control signal used for co-ordinated defrost
control to hold cabinets from returning to normal re-
frigeration after a defrost until all cabinets have termi-
nated defrost.
0=OFF, 1=ON
x11
--- HoldAfterDef
MC Stop defrost
Master control signal used to prevent a defrost start in
a controller.
0=OFF, 1=ON
x12
--- Disable def.
MC Light signal
Master control signal for control of light via a data
communication signal from the system manager.
0=OFF, 1=ON
o39
o39 Light remote
MC Actual dewpoint
Master control signal sending the actual measured
dewpoint from the system manager to the controller
over the network.
x03
--- Act.DewPoint
MC Po load factor
x83
--- Load factor
MC Key/Bluetooth
lock
Master control signal that will lock down all Bluetooth
data communication and optionally also the opera-
tion of the display keys (depend upon selection in
P89 Display keyboard lock).
0=OFF, 1=ON
aaa
--- Key/BT Lock
MC Load request
Master control signal used to control the load balance
between multiple case controllers on the same suc-
tion line
x82
--- LoadReq
MC Force cond. fan
Master control signal for starting condenser fan in
plug-in cabinets in order to reclaim heat in the store.
0=OFF, 1=ON
x85
--- Cond. Fan
Fault message
In an error situation the alarm LED on the front will be on and the alarm relay will be activated (depending on
priority). If you push the alarm button for 3 seconds you can see the alarm report in the display. (Alarm priorities can
be changed. See the Alarm relay priorities.) Here are the messages that may appear:
Table 37: Fault message
Code
Alarm text
Description
E01
Hardware failure
The controller has a hardware failure
E06
Clock lost time
Clock has lost valid time
E25
S3 Air ON evap. A - sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E26
S4 Air OFF evap. A - sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E27
S5 Evaporator A - sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E50
S7 Brine inlet temp. sensor error
Sensor signal is out of range. Please check the sensor for correct operation
E65
S8 Brine outlet temp. sensor error
Sensor signal is out of range. Please check the sensor for correct operation
A01
High temperature alarm A
The alarm temperature has been above the max alarm limit for a longer time period than the set alarm de-
lay.
A02
Low temperature alarm A
The alarm temperature has been below the min alarm limit for a longer time period than the set alarm de-
lay.
A04
Door open alarm
The door has been open for a too long time
A05
Max defrost hold time exceeded
The controller has been waiting longer time than permitted after a co-ordinated defrost.
A15
DI alarm 1
Alarm signal from digital input signal
A16
DI alarm 2
Alarm signal from digital input signal
A19
Compressor safety alarm
Alarm from digital input monitoring function
A45
Main switch set OFF
The controller manin switch has been set to either Stop or Manaual control. Alternatively a digital input set
up for "main switch" function, has stopped control
A59
Case in cleaning mode
A case cleaning operation has been started on a case
A93
Speed drive alarm
Alarm from digital input monitoring function
AA3
Refrigerant leak detected
Refrigerant is leaking from the refrigeration system
AA4
S7 Max. brine temp.
The S7 brine temperature has exceeded the set maximum temperature alarm limit
a04
Wrong IO
conguration
Inputs and outputs have not been
congured correctly
Z01
Max defrost time exceeded A
The last defrost cycle has stopped on time instead of set temperature
NOTE:
Data communication
The importance of individual alarms can be dened with a setting. The setting must be carried out in the group
"Alarm destinations".
AK-CC55 Water Loop