Function
Values
R-W
Code
1
2
3
4
5
6
7
8
Min.value
Max.value
Fact.value
Oil return speed
1-2
P79
*
*
P77
100 %
50%
Oil return time period
1-2
P80
*
*
10 s
600 s
60 s
Rail heat PWM - Period time
1-2
P82
*
*
*
*
4 s
60 s
10 s
Access code 1
1-1
P88
*
*
*
*
*
*
*
*
0
999
0
Display keyboard lock
0=None, 1=Local, 2=Net-
work
1-2
P89
*
*
*
*
*
*
*
*
0
2
0
AO1 Min. frequency
1-3
(1)
P95
*
*
*
*
0 Hz
P96
50Hz
AO1 Max. frequency
1-3
(1)
P96
*
*
*
*
P95
500 Hz
100Hz
AO1 PWM frequency
1-3
(1)
P97
*
*
*
*
100 Hz
500 Hz
200Hz
AO1 Invert signal
0=No, 1=Yes
1-3
(1)
P98
*
*
*
*
0
1
0
Condenser sensors
0=None, 1=S7, 2=S7 and S8
1-3
(1)
P99
*
*
*
*
*
*
*
*
0
2
1
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
DO cong and manual
Table 17: DO cong and manual
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
Min.value
Max.value
Fact.value
DO2 Conguration
0=None, 1=Fans, 2=Fan ECO,
3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds,
10=Air heater, 12=Condens-
er fan
1-3
(1)
q02
*
*
*
*
0
12
5
DO3 Conguration
0=None, 1=Fans, 2=Fan ECO,
3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds,
10=Air heater, 12=Condens-
er fan
1-3
(1)
q03
*
*
*
*
0
12
1
DO4 Conguration
0=None, 1=Fans, 2=Fan ECO,
3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds,
10=Air heater, 12=Condens-
er fan
1-3
(1)
q04
*
*
*
0
12
6
DO5 Conguration
0=None, 1=Fans, 2=Fan ECO,
3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds,
10=Air heater, 12=Condens-
er fan
1-3
(1)
q05
*
*
*
*
0
12
3
AO1 Conguration
0=None, 1=Rail heat PWM,
3=Comp. speed, 4=Brine
pump speed
1-3
(1)
q09
*
*
*
*
0
4
0
Compressor 1 - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q12
*
*
*
*
*
*
0
1
0
Fan - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q13
*
*
*
*
*
*
*
*
0
1
0
Defrost A - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q14
*
*
*
*
*
*
*
*
0
1
0
Rail heat - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q15
*
*
*
*
0
1
0
Alarm relay - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q16
*
*
*
*
*
*
*
*
0
1
0
Light - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q17
*
*
*
*
*
*
*
0
1
0
Compressor 2 - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q19
*
*
0
1
0
Blinds - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q21
*
*
*
*
0
1
0
Air heater - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q23
*
*
*
*
0
1
0
Fan ECO - override
0=MAN OFF, 1=MAN ON
1-2
(2)
q24
*
*
*
*
0
1
0
Rail heat PWM - override
1-2
(2)
q27
*
*
*
*
0 %
100 %
0%
High temperature - Priority
0=Disabled, 3=Low, 2=Medi-
um, 1=High
1-2
q28
*
*
*
*
*
*
*
*
0
3
1
Low temperature - Priority
0=Disabled, 3=Low, 2=Medi-
um, 1=High
1-2
q29
*
*
*
*
*
*
*
*
0
3
1
Sensor errors - Priority
0=Disabled, 3=Low, 2=Medi-
um, 1=High
1-2
q30
*
*
*
*
*
*
*
*
0
3
1
DI alarms - Priority
0=Disabled, 3=Low, 2=Medi-
um, 1=High
1-2
q31
*
*
*
*
*
*
*
*
0
3
2
Defrost - Priority
0=Disabled, 3=Low, 2=Medi-
um, 1=High
1-2
q32
*
*
*
*
*
*
*
*
0
3
3
Miscellaneous - Priority
0=Disabled, 3=Low, 2=Medi-
um, 1=High
1-2
q33
*
*
*
*
*
*
*
*
0
3
2
AK-CC55 Water Loop
© Danfoss | Climate Solutions | 2022.04 BC378540472015en-000101 | 44