Function
Description
Values
Code
Short name
Display readout ad-
justment
Correction of the display´s temperature.If the temper-
ature at the products and the temperature received
by the controller are not identical, an oset adjust-
ment of the display temperature can be carried out.
r04
r04 Disp. Adj. K
Temperature unit
Select whether temperatures are to be shown as °C or
as °F.
0=Celsius, 1=Fahrenheit
r05
r05 Temp.unit
Display keyboard
lock
With this setting it is possible to lock the keyboard
operation of the local display.
None: Display keyboard operation will never be
locked.
Local: When not used for some time, the local display
will lock the keyboard operations and a special key
combination is required in order to enable the key-
board operations.
Network: When the controller receives a master con-
trol signal (--- Key/BT lock) via the network, the dis-
play keyboard operations will be locked. The key-
board operations can only be activated again by set-
ting the master control signal OFF via the System
Manager.
0=None, 1=Local, 2=Network
P89
P89 LockDispKey
Alarm relay priorities
Table 31: Alarm relay priorities
Function
Description
Values
Code
Short name
Alarm relay
Actual status of output function
0=OFF, 1=ON
u62
u62 Alarm relay
Alarm relay priority
Set which alarm priorities that are to activate the
alarm relay: 0=Not used, alarm relay is not used1:
High. Alarm with high priority will activate relay2: Me-
dium. Alarms with high or medium priority will acti-
vate the alarm relay3: All. All alarms will activate alarm
relay
0=Not used, 1=High Priority, 2=Medium priority,
3=All
P41
P41 Al.Rel.Prio
Mute alarm
When muting alarms, the alarm relay will stop signal-
ling the alarm until a new alarm arises
0=OFF, 1=ON
q38
q38 Mute Alarm
High temperature -
Priority
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
q28
q28 Hi Temp Prio
Low temperature -
Priority
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
q29
q29 Lo Temp Prio
Sensor errors - Prior-
ity
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
q30
q30 Sensor Prio
DI alarms - Priority
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
q31
q31 DIAlarm Prio
Defrost - Priority
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
q32
q32 Defrost Prio
Miscellaneous - Pri-
ority
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
q33
q33 Misc Prio
Control stopped -
Priority
Select the priority of the alarms assigned to the alarm
group. Be aware - by selecting "Disable", the alarms
will not be shown on the display or be routed to the
alarm relay or to the network.
0=Disabled, 3=Low, 2=Medium, 1=High
q35
q35 CtrlOFF Prio
AK-CC55 Water Loop
© Danfoss | Climate Solutions | 2022.04 BC378540472015en-000101 | 58