Time in hours for start of defrost
Time in minutes for when defrost cycle is to be star-
ted
Wednesday - Follow
schedule
Thursday - Follow
schedule
Saturday - Follow
schedule
Compressor/Pump control
Table 25: Compressor/Pump control
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip o, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 17=Door open, 18=Melt
period, 19=Modulating temp. control, 20=Emergency
control, 25=Manual control, 29=Case cleaning,
30=Forced cooling, 32=Power-up delay, 33=Air heat-
ing, 34=Comp. safety cut-out, 45=Shut down control-
ler, 50=High S7 Brine inlet
Readout of the actual cut-in value for the thermostat
Readout of the actual cut-out value for the thermo-
stat
Actual status of output function
Actual status of output function
Actual status of output function
Actual status of output function
Actual status of output function
Minimum time the compressor is to run once it has
been started.
Minimum time the compressor has to be stopped
Time delay for couplings of two compressors. The
step delay is the time that has to elapse from the rst
compressor cuts in and until the next compressor can
cut in.
Selection of step control mode for compressors. At se-
quential mode compressor 1 will always be the rst to
start and the last to stop. In cyclic mode the run time
between the compressor will be equalized.
Select whether compressor 2 is to be in operation in
thermostat band 2
The minimum allowed speed
The requested start speed (must be set to a higher
value than “Min. speed”). After start, this speed is
maintained for 10 seconds before speed control is
started
The maximum allowed speed
The compressor will run with the dened speed dur-
ing the hot gas defrost
Limitation on how fast the speed can ramp up/down
(set in % per. second)
AK-CC55 Water Loop