AK-CC55 Connect menu (SW ver. 1.2x)
Start / Stop
Table 19: Start / Stop
Start / stop of refrigeration. With this setting refrigera-
tion can be started, stopped or a manual override of
the outputs can be allowed. (For manual control the
value is set at -1). Then the outputs can be force con-
trolled. Start / stop of refrigeration can also be accom-
plished with the external switch function connected
to a DI input.Stopped control will give a ”Main switch
OFF" alarm.
-1=Manual, 0=Stop, 1=Start
Delay of outputs at
power-up
Delay of output signal after start-up After start-up or a
power failure the controller’s functions can be de-
layed so that overloading of the electricity supply net-
work is avoided. Here you can set the time delay.
Conguration
Table 20: Conguration
Start / stop of refrigeration. With this setting refrigera-
tion can be started, stopped or a manual override of
the outputs can be allowed. (For manual control the
value is set at -1). Then the outputs can be force con-
trolled. Start / stop of refrigeration can also be accom-
plished with the external switch function connected
to a DI input.Stopped control will give a ”Main switch
OFF" alarm.
-1=Manual, 0=Stop, 1=Start
Selection of application The controller covers several
applications for control of a refrigerated case. Here
you set which of the possible applications is re-
quired.This menu can only be set when regulation is
stopped, i.e. “r12 Main Switch” is set to 0.
1=1: One comp., 2=2: One comp. custom, 3=3: Two
comp., 4=4: Two comp. custom, 5=5: Speed comp.,
6=6: Speed comp. custom, 7=7: Speed pump, 8=8:
Speed pump custom
Select if an additional S8 Brine outlet sensor is to be
used as monitoring sensor for the brine cooled con-
denser.
0=None, 1=S7, 2=S7 and S8
Select the function of the digital output
0=None, 1=Fans, 2=Fan ECO, 3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds, 10=Air heater, 12=Con-
denser fan
Select the function of the digital output
0=None, 1=Fans, 2=Fan ECO, 3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds, 10=Air heater, 12=Con-
denser fan
Select the function of the digital output
0=None, 1=Fans, 2=Fan ECO, 3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds, 10=Air heater, 12=Con-
denser fan
Select the function of the digital output
0=None, 1=Fans, 2=Fan ECO, 3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds, 10=Air heater, 12=Con-
denser fan
Select the function of the analogue output
0=None, 1=Rail heat PWM, 3=Comp. speed, 4=Brine
pump speed
Select the signal type of the analogue output
0=None, 1=Voltage, 2=Frequency, 3=PWM
Minimum voltage signal of the analogue output
Maximum voltage signal of the analogue output
Minimum frequency signal of the analogue output
Maximum frequency signal of the analogue output
Frequency of the PWM signal from the analogue out-
put
Option for inverting the analogue output signalt
Select the function of the digital input
0=None, 1=DI status, 2=Door function, 3=Door alarm,
4=Defrost start, 5=Main switch, 6=Night setback,
7=Thermostat band, 8=Alarm at closed, 9=Alarm at
open, 10=Case cleaning, 11=Forced cooling,
12=Open blinds, 15=Shutdown, 16=Light control,
20=Leak detection, 24=Comp. safety, 25=Speed drive
alarm, 26=Force cond. fan ON, 29=Door fan stop
AK-CC55 Water Loop