AK-CC55 Connect menu (SW ver. 1.2x)
Start / Stop
Table 19: Start / Stop
Function
Description
Values
Code
Short name
Main switch
Start / stop of refrigeration. With this setting refrigera-
tion can be started, stopped or a manual override of
the outputs can be allowed. (For manual control the
value is set at -1). Then the outputs can be force con-
trolled. Start / stop of refrigeration can also be accom-
plished with the external switch function connected
to a DI input.Stopped control will give a ”Main switch
OFF" alarm.
-1=Manual, 0=Stop, 1=Start
r12
r12 Main switch
Delay of outputs at
power-up
Delay of output signal after start-up After start-up or a
power failure the controller’s functions can be de-
layed so that overloading of the electricity supply net-
work is avoided. Here you can set the time delay.
o01
o01 DelayOfOutp.
Conguration
Table 20: Conguration
Function
Description
Values
Code
Short name
Main switch
Start / stop of refrigeration. With this setting refrigera-
tion can be started, stopped or a manual override of
the outputs can be allowed. (For manual control the
value is set at -1). Then the outputs can be force con-
trolled. Start / stop of refrigeration can also be accom-
plished with the external switch function connected
to a DI input.Stopped control will give a ”Main switch
OFF" alarm.
-1=Manual, 0=Stop, 1=Start
r12
r12 Main switch
Application mode
Selection of application The controller covers several
applications for control of a refrigerated case. Here
you set which of the possible applications is re-
quired.This menu can only be set when regulation is
stopped, i.e. “r12 Main Switch” is set to 0.
1=1: One comp., 2=2: One comp. custom, 3=3: Two
comp., 4=4: Two comp. custom, 5=5: Speed comp.,
6=6: Speed comp. custom, 7=7: Speed pump, 8=8:
Speed pump custom
o61
o61 Appl. mode
Condenser sensors
Select if an additional S8 Brine outlet sensor is to be
used as monitoring sensor for the brine cooled con-
denser.
0=None, 1=S7, 2=S7 and S8
P99
P99 Cond Sensors
DO2 Conguration
Select the function of the digital output
0=None, 1=Fans, 2=Fan ECO, 3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds, 10=Air heater, 12=Con-
denser fan
q02
q02 DO2 Cong.
DO3 Conguration
Select the function of the digital output
0=None, 1=Fans, 2=Fan ECO, 3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds, 10=Air heater, 12=Con-
denser fan
q03
q03 DO3 Cong.
DO4 Conguration
Select the function of the digital output
0=None, 1=Fans, 2=Fan ECO, 3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds, 10=Air heater, 12=Con-
denser fan
q04
q04 DO4 Cong.
DO5 Conguration
Select the function of the digital output
0=None, 1=Fans, 2=Fan ECO, 3=Defrost, 4=Rail heat,
5=Alarm, 6=Light, 7=Blinds, 10=Air heater, 12=Con-
denser fan
q05
q05 DO5 Cong.
AO1 Conguration
Select the function of the analogue output
0=None, 1=Rail heat PWM, 3=Comp. speed, 4=Brine
pump speed
q09
q09 AO1 Cong.
AO1 Signal type
Select the signal type of the analogue output
0=None, 1=Voltage, 2=Frequency, 3=PWM
o09
o09 AO1 Signal
AO1 Min. voltage
Minimum voltage signal of the analogue output
o27
o27 AO1 Min volt
AO1 Max. voltage
Maximum voltage signal of the analogue output
o28
o28 AO1 Max volt
AO1 Min. frequency
Minimum frequency signal of the analogue output
P95
P95 AO1 Min freq
AO1 Max. frequency
Maximum frequency signal of the analogue output
P96
P96 AO1 Max freq
AO1 PWM frequen-
cy
Frequency of the PWM signal from the analogue out-
put
P97
P97 AO1 PWM Freq
AO1 Invert signal
Option for inverting the analogue output signalt
0=No, 1=Yes
P98
P98 AO1 Invert
DI1 Conguration
Select the function of the digital input
0=None, 1=DI status, 2=Door function, 3=Door alarm,
4=Defrost start, 5=Main switch, 6=Night setback,
7=Thermostat band, 8=Alarm at closed, 9=Alarm at
open, 10=Case cleaning, 11=Forced cooling,
12=Open blinds, 15=Shutdown, 16=Light control,
20=Leak detection, 24=Comp. safety, 25=Speed drive
alarm, 26=Force cond. fan ON, 29=Door fan stop
o02
o02 DI1 Cong.
AK-CC55 Water Loop
© Danfoss | Climate Solutions | 2022.04 BC378540472015en-000101 | 48