Function
Description
Values
Code
Short name
DI2 Conguration
Select the function of the digital input
0=None, 1=DI status, 2=Door function, 3=Door alarm,
4=Defrost start, 5=Main switch, 6=Night setback,
7=Thermostat band, 8=Alarm at closed, 9=Alarm at
open, 10=Case cleaning, 11=Forced cooling,
12=Open blinds, 13=Coordinated defrost, 15=Shut-
down, 16=Light control, 20=Leak detection,
24=Comp. safety, 25=Speed drive alarm, 26=Force
cond. fan ON, 29=Door fan stop
o37
o37 DI2 Cong.
Temperature sensor
type
Sensor type for S3, S4 and S5. Normally a Pt 1000 sen-
sor with great signal accuracy is used. But you can al-
so use a sensor with another signal accuracy. That
could e.g. be a PTC sensor (1000 ohm at 25 °C). All the
mounted sensors S3-S5 must be of the same type.
0=Pt 1000, 1=PTC 1000, 2=NTC 5k, 3=NTC 10k,
4=User-dened
o06
o06 SensorCong
Sensor point 1 - Temp.
The temperature value for the user-dened tempera-
ture sensor in the reference point
X20
--- SP1 Temp
Sensor point 1 - kohm
The resistance value in kohm for the user-dened
temperature sensor in the reference point
X21
--- SP1 kohm
Sensor point 1 - ohm
The resistance value in ohm for the user-dened tem-
perature sensor in the reference point
X22
--- SP1 ohm
Sensor point 2 - Temp.
The temperature value for the user-dened tempera-
ture sensor in the reference point
X23
--- SP2 Temp
Sensor point 2 - kohm
The resistance value in kohm for the user-dened
temperature sensor in the reference point
X24
--- SP2 kohm
Sensor point 2 - ohm
The resistance value in ohm for the user-dened tem-
perature sensor in the reference point
X25
--- SP2 ohm
Sensor point 3 - Temp.
The temperature value for the user-dened tempera-
ture sensor in the reference point
X26
--- SP3 Temp
Sensor point 3 - kohm
The resistance value in kohm for the user-dened
temperature sensor in the reference point
X27
--- SP3 kohm
Sensor point 3 - ohm
The resistance value in ohm for the user-dened tem-
perature sensor in the reference point
X28
--- SP3 ohm
Defrost method
Select method of defrost
0=None, 1=Electrical, 2=Hot gas, 4=Air/Ocycle
d01
d01 Def. method
Defrost stop meth-
od
Here you dene whether a defrost cycle is to be stop-
ped by time or by a temperature sensor
0=Time, 1=S5 sensor, 2=S4 sensor
d10
d10 DefStopSens.
Defrost stop limit A
When the selected defrost stop sensor reaches the set
limit, the defrost cycle is terminated
d02
d02 Def.StopTemp
Food type
When changing the food type the controller will auto-
matically adapt temperature setpoints and alarm lim-
its according to the selected food type. Please be
aware that the setting will revert to "None" after hav-
ing been changed.
0=None, 1=Vegetables, 2=Dairy, 3=Meat and sh,
4=Frozen food, 5=Ice cream
r89
r89 Food type
Food temp. sensor
Select the temperature to be used for the food tem-
perature representation
1=Thermostat air, 2=Alarm air, 3=S3 Air ON evap.
q39
q39 Food sensor
Network address
Network address of the controller
o03
o03 Unit addr.
DO1 Function
Function associated to the physical input/output
U61
U61 DO1 Cong.
DO2 Function
Function associated to the physical input/output
U62
U62 DO2 Cong.
DO3 Function
Function associated to the physical input/output
U63
U63 DO3 Cong.
DO4 Function
Function associated to the physical input/output
U64
U64 DO4 Cong.
DO5 Function
Function associated to the physical input/output
U65
U65 DO5 Cong.
DI1 Function
Function associated to the physical input/output
Y55
DI1 Cong
DI2 Function
Function associated to the physical input/output
Y56
DI2 Cong
AI1 Function
Function associated to the physical input/output
Y58
AI1 Cong
AI2 Function
Function associated to the physical input/output
Y59
AI2 Cong
AI3 Function
Function associated to the physical input/output
Y60
AI3 Cong
AI4 Function
Function associated to the physical input/output
Y61
AI4 Cong
AI5 Function
Function associated to the physical input/output
Y62
AI5 Cong
AO1 Function
Function associated to the physical input/output
U69
U69 AO1 Cong.
© Danfoss | Climate Solutions | 2022.04 BC378540472015en-000101 | 49