Fan control
Table 13: Fan control
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
Min.value
Max.value
Fact.value
Fan stop high S5 temp.
1-2
F04
*
*
*
*
*
*
*
*
-50.0 °C
50.0 °C
50.0 °C
Fan pulsing mode
0=No pulsing, 1=Pulsing
cut-out, 2=Pulsing cut-out
night
1-2
F05
*
*
*
*
*
*
*
*
0
2
0
Fan period time
1-2
F06
*
*
*
*
*
*
*
*
1 min
30 min
5 min
Fan ON cycle
1-2
F07
*
*
*
*
*
*
*
*
0 %
100 %
100%
Cond. fan cut-in
1-2
F24
*
*
*
*
10.0 °C
110.0 °C
60.0 °C
Cond. fan di.
1-2
F25
*
*
*
*
1.0 °C
20.0 °C
5.0 °C
Defrost schedule
Table 14: Defrost schedule
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
Min.value
Max.value
Fact.value
Defrost schedule
0=No, 1=Yes
1-2
t00
*
*
*
*
*
*
*
*
0
1
0
Def. start 1 - h
1-2
t01
*
*
*
*
*
*
*
*
0 h
23 h
0h
Def. start 1 - min
1-2
t11
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 2 - h
1-2
t02
*
*
*
*
*
*
*
*
0 h
23 h
0h
Def. start 2 - min
1-2
t12
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 3 - h
1-2
t03
*
*
*
*
*
*
*
*
0 h
23 h
0h
Def. start 3 - min
1-2
t13
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 4 - h
1-2
t04
*
*
*
*
*
*
*
*
0 h
23 h
0h
Def. start 4 - min
1-2
t14
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 5 - h
1-2
t05
*
*
*
*
*
*
*
*
0 h
23 h
0h
Def. start 5 - min
1-2
t15
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Def. start 6 - h
1-2
t06
*
*
*
*
*
*
*
*
0 h
23 h
0h
Def. start 6 - min
1-2
t16
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Time h
0-1
t07
*
*
*
*
*
*
*
*
0 h
23 h
0h
Time min
0-1
t08
*
*
*
*
*
*
*
*
0 min
59 min
0 min
Time date
0-1
t45
*
*
*
*
*
*
*
*
1
31
1
Time month
0-1
t46
*
*
*
*
*
*
*
*
1
12
1
Time year
0-1
t47
*
*
*
*
*
*
*
*
0
100
0
Monday - Follow schedule
0=No, 1=Yes
1-2
t51
*
*
*
*
*
*
*
*
0
1
1
Tuesday - Follow schedule
0=No, 1=Yes
1-2
t52
*
*
*
*
*
*
*
*
0
1
1
Wednesday - Follow sched-
ule
0=No, 1=Yes
1-2
t53
*
*
*
*
*
*
*
*
0
1
1
Thursday - Follow schedule
0=No, 1=Yes
1-2
t54
*
*
*
*
*
*
*
*
0
1
1
Friday - Follow schedule
0=No, 1=Yes
1-2
t55
*
*
*
*
*
*
*
*
0
1
1
Saturday - Follow schedule
0=No, 1=Yes
1-2
t56
*
*
*
*
*
*
*
*
0
1
1
Sunday - Follow schedule
0=No, 1=Yes
1-2
t57
*
*
*
*
*
*
*
*
0
1
1
Miscellaneous
Table 15: Miscellaneous
Function
Values
R-W
Code
1
2
3
4
5
6
7
8
Min.value
Max.value
Fact.value
Delay of outputs at power-
up
1-2
o01
*
*
*
*
*
*
*
*
0 s
600 s
5 s
DI1
Conguration
0=None, 1=DI status,
2=Door function, 3=Door
alarm, 4=Defrost start,
5=Main switch, 6=Night set-
back, 7=Thermostat band,
8=Alarm at closed, 9=Alarm
at open, 10=Case cleaning,
11=Forced cooling,
12=Open blinds, 15=Shut-
down, 16=Light control,
20=Leak detection,
24=Comp. safety, 25=Speed
drive alarm, 26=Force cond.
fan ON, 29=Door fan stop
1-2
(1)
o02
*
*
*
*
*
*
*
*
0
29
0
Network address
1-3
(1)
o03
*
*
*
*
*
*
*
*
0
240
0
AK-CC55 Water Loop
© Danfoss | Climate Solutions | 2022.04 BC378540472015en-000101 | 42