0=Pt 1000, 1=PTC 1000,
2=NTC 5k, 3=NTC 10k,
4=User-dened
0=None, 1=Voltage, 2=Fre-
quency, 3=PWM
0=None, 1=DI status,
2=Door function, 3=Door
alarm, 4=Defrost start,
5=Main switch, 6=Night set-
back, 7=Thermostat band,
8=Alarm at closed, 9=Alarm
at open, 10=Case cleaning,
11=Forced cooling,
12=Open blinds, 13=Coordi-
nated defrost, 15=Shut-
down, 16=Light control,
20=Leak detection,
24=Comp. safety, 25=Speed
drive alarm, 26=Force cond.
fan ON, 29=Door fan stop
1=Day and night, 2=Net-
work, 3=Door switch, 4=Net-
work (Fallback), 5=Digital in-
put
0=OFF, 1=Fans run, 2=Clean-
ing
1=1: One comp., 2=2: One
comp. custom, 3=3: Two
comp., 4=4: Two comp. cus-
tom, 5=5: Speed comp., 6=6:
Speed comp. custom, 7=7:
Speed pump, 8=8: Speed
pump custom
0=ON, 1=Day/Night timer,
2=Dewpoint ctrl.
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
(1)
In order to change this parameter the regulation must be stopped via the parameter r12 Main switch = OFF.
Control
Table 16: Control
0=Not used, 1=High Priority,
2=Medium priority, 3=All
Fan stop at blinds closing
© Danfoss | Climate Solutions | 2022.04 BC378540472015en-000101 | 43
AK-CC55 Water Loop